R3-NM1
P. / 7
EM-8354 Rev.4
*2. Refer to the specifications of the related series for the
Data Allocation Type of I/O modules.
• Dual Communication
: SW3
When two network modules are mounted, one must be
‘Main’ (OFF) network and the other must be ‘Sub’ (ON) net-
work. For single communication, the network module must
always be set to ‘Main’ (OFF).
• Input Error Data
: SW3
Hold
: When the communication from an input module is lost
due to the input module error, the network module holds the
signal and stands by until the communication recovers.
Set to ‘0’
: When the communication from an input module
is lost due to the input module error, the network module
outputs ‘0.’
COMPONENT IDENTIFICATION
■
SIDE DIP SW
• Data allocation
: SW1, SW2
Data Allocation Type*
2
must be assigned to each I/O module
slot position to specify how many data areas (four types) are
to be occupied by each.
Two bits from SW1 and SW2 are assigned to each position,
and data areas can be specified from the slot No. 1 through
8. Setting for No. 9 and later slots is identical to No. 8.
RUN LED
■
FRONT VIEW
■
SIDE VIEW
ERR LED
SA1
SA2
1
2
3
4
5
6
Terminal Block
Node Address (MSD)
Node Address (LSD)
Transmission Properties
Configuration Jack
5
4 3 2 1
0
9
8
7
6
5
4 3 2 1
0
9
8
7
6
SW6
ON
8
7
6
5
4
3
2
1
FG
SLD
DG
DB
DA
SW2
ON
8
7
6
5
4
3
2
1
SW3
ON
4
3
2
1
ON
8
7
6
5
4
3
2
1
SW1
Functions
■
FRONT ROTARY SW
Set the module’s node address in hexadecimal with SA1 and
SA2.
■
FRONT DIP SW
• Baud rate
: SW6
• Parity
: SW6 *
1
• Data Mode
: SW6 *
1
*1. Bit assignment according to Parity and Data Mode setting
BAUD RATE (bps)
38.4k
(*)
19.2k
9600
4800
SW6-1
OFF
ON
OFF
ON
SW6-2
OFF
OFF
ON
ON
PARITY
None
(*)
Odd
Even
N/A
SW6-3
OFF
ON
OFF
ON
SW6-4
OFF
OFF
ON
ON
DATA MODE
RTU (Binary)
(*)
ASCII
SW6-5
OFF
ON
(*) Factory setting
MODE
START
DATA
PARITY
STOP
RTU
1
8
1
1
1
8
None
2
ASCII
1
7
1
1
1
7
None
2
SW ASSIGNMENT
SLOT
SW1-1
SW1-2
1
SW1-3
SW1-4
2
SW1-5
SW1-6
3
SW1-7
SW1-8
4
SW2-1
SW2-2
5
SW2-3
SW2-4
6
SW2-5
SW2-6
7
SW2-7
SW2-8
8
SW SETTING
DATA ALLOCATION
OFF
OFF
1
ON
OFF
4
OFF
ON
8
ON
ON
16
DUAL COMMUNICATION
Main
(*)
Sub
SW3-1
OFF
ON
INPUT ERROR DATA
Hold
(*)
Set to ‘0’
SW3-2
OFF
ON