background image

R3-NF2

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8438   Rev.1  P. 4 / 5

TRANSMISSION DATA DESCRIPTIONS

This module allocates T-link addresses in order from slot 1.  Set the begin address to the module’s node address (T-Link ad-
dress.) 
For example; if the formation of the I/O modules is: slot 1: R3-SV4, slot 2: R3-YV4, slot 3: R3-DA16 and slot 4: R3-DC16, the 
I/O data is assigned as detailed on the table below.  Set “10” to the module address.  Discrete I/O data can be also represented 
with  bit address.  Ch.1 through 16 are assigned to 0 thr. F.

SLOT

MODULE

ADDRESS

WORD ADDRESS

CONTENTS

1

R3-SV4

10

0

CH1 input data

1

CH2 input data

2

CH3 input data

3

CH4 input data

2

R3-YV4

11

0

CH1 output data

1

CH2 output data

2

CH3 output data

3

CH4 output data

3

R3-DA16

12

0

Input data

4

R3-DC16

13

0

Output data

SYSTEM DEFINITIONS

• Registration of R3-NF2

Specify as follows: Module type: Slave; Outline: T-Link i/f unit (FTL); T-link address: Node address (rotary sw.)

• Registration of I/O module

Select “Remote I/O” for the type of module.  Configure on the parameters the data size of the I/O modules.  Refer to each 
module’s data allocation area value for the data size setting; except for the modules detailed below, of which data size is not 
related to the allocation area value.

MODEL

TYPE

DATA SIZE (WORDS)

Input

Output

R3-DA32A, R3-Ax8

Digital input

2

0

R3-DC32x

Digital output

0

2

R3x-DAC16x, R3x-RR8, R3-PD16x

Digital input/output

1

1

R3-BA32A

Analog input

2

0

R3-BC32A

Analog output

0

2

Reviews: