COMPONENT IDENTIFICATION

1

2

3

4

5

6

SW3

ON

4

3

2

1

ON

8

7

6

5

4

3

2

1

SW1

 

SIDE VIEW

 

FRONT VIEW

LED

Functions

Module

Allocation

Functions

RUN LED

ERR LED

Configuration Jack

RJ-45 Modular Jack

Rotary SW (unused)

Rotary SW (unused)

Ethernet Indicator

LINK

DPLX (Duplex)
LINK10 (10Mbps)

LINK100 (100Mbps)

COL (Collision)

8

67

345 2

1 0

F

E

D

C

B

A9

8

67

345 2

1 0

F

E

D

C

B

A9

 

ETHERNET INDICATOR

ID

COLOR

FUNCTION

LINK

Red

ON at LINK

DPLX

Red

ON at full-duplex communication

LINK10

Red

ON at 10 Mbps connection

LINK100

Red

ON at 100 Mbps connection

COL

Red

Blink at collision

 

SIDE DIP SW

(*) Factory setting

• Module Allocation: SW1-1, 1-2, 1-3

MODULE

SW1-1

SW1-2

SW1-3

1

OFF(*)

OFF(*)

OFF(*)

2

ON

OFF

OFF

3

OFF

ON

OFF

4

ON

ON

OFF

5

OFF

OFF

ON

6

ON

OFF

ON

7

OFF

ON

ON

8

ON

ON

ON

• LED Function: SW3-4

Functions assigned to the front RUN and ERR LEDs can 
be selected.

SW3-4

LED FUNCTION

RUN

ERR

OFF(*)

Green turns ON when 
Modbus/TCP commu-
nication is normal and 
fieldbus communication 
on the R3 Network mod-
ule side is also normal

Green turns ON/blinks 
in communication errors 
(OFF with wire break-
down; Green blinks with 
setting errors)

ON

Red turns ON when 
receiving data

Red turns ON when 
transmitting data

Note:  Be sure to set unused SW1-4 through 1-8 and SW3-1 

through 3-3 to OFF.

PC CONFIGURATOR

With the configurator software (model: R3CON), parameters shown below are configurable.
Refer to the users manual of R3CON for detailed operation.

 

INTERFACE SETTING 

PARAMETER

SETTING RANGE

DEFAULT SETTING

Time

0.2 – 3200.0 (sec.)

3.0 (sec.) 

IP Address 

0.0.0.0 – 255.255.255.255

192.168.0.1

Subnet Mask

0.0.0.0 – 255.255.255.255

255.255.255.0

TCP Socket: Port1 to Port4

0 – 32767

502

Linger: 1 to 4 

0.0 – 3276.7 (sec.)

180.0 (sec.)

Summary of Contents for R3-GE1

Page 1: ...it inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration Do not apply physical impact to the unit Environmental temperature must be wi...

Page 2: ...F OFF OFF 2 ON OFF OFF 3 OFF ON OFF 4 ON ON OFF 5 OFF OFF ON 6 ON OFF ON 7 OFF ON ON 8 ON ON ON LED Function SW3 4 Functions assigned to the front RUN and ERR LEDs can be selected SW3 4 LED FUNCTION R...

Page 3: ...N DIAGRAM 1 4 Modbus TCP RJ 45 MODULAR JACK INTERNAL BUS INTERNAL POWER BUS CONNECTOR RUN RUN JACK RUN CONTACT OUTPUT CONFIGURATION JACK WIRING INSTRUCTIONS M3 SCREW TERMINAL Torque 0 5 N m SOLDERLESS...

Page 4: ...ith 32 bytes of data Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Ping statistics for Packets Sen...

Page 5: ...ram Controller 14 Poll Controller 15 Force Multiple Coils X Digital output from the slave 16 Preset Multiple Registers X General purpose register within the slave 17 Report Slave ID Slave type RUN sta...

Page 6: ...17 448 6 449 480 7 481 512 8 Holding Registers 4X 1 16 I Analog Output 1 17 32 2 33 48 3 49 64 4 65 80 5 81 96 6 97 112 7 113 128 8 257 288 F Analog Output 1 289 320 2 321 352 3 353 384 4 385 416 5 41...

Page 7: ...l bus error occurs and the ERR LED turns on Max 16 real I O modules and virtual modules are available The interface module can not read the data for more than 16 modules WHEN R3 GE1 IS MOUNTED ON SLOT...

Reviews: