R3-CZ4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax:
+81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8447 Rev.2 P. 2 / 3
COMPONENT IDENTIFICATION
ON
8
7
6
5
4
3
2
1
SW1
SW2
ON
8
7
6
5
4
3
2
1
SW3
ON
4
3
2
1
1
2
3
4
5
6
7
8
9
10
■
FRONT VIEW
■
SIDE VIEW
ERR LED
RUN LED
Conv.
Rate
Input 2 (SW1)
or
Input 4 (SW2)
Range
Input 1 (SW1)
or
Input 3 (SW2)
Functions
■
STATUS INDICATOR LED
RUN indicator:
Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator:
Bi-color (red/green) LED;
Red with the input abnormality;
Green in normal operating conditions.
■
SIDE DIP SW
•
Input Range: SW1, SW2
INPUT 1 (SW 1)
INPUT 2 (SW 1)
RANGE
INPUT 3 (SW 2)
INPUT 4 (SW 2)
1
2
3
4
5
6
7
8
OFF OFF OFF OFF OFF OFF OFF OFF 0 – 1.5mA (*)
ON OFF OFF OFF ON OFF OFF OFF 0 – 0.1mA
•
Conversion Rate: SW3
SW
CONVERSION RATE
80 ms (
*
)
40 ms
20 ms
10 ms
SW3-1
OFF
ON
OFF
ON
SW3-2
OFF
OFF
ON
ON
(*) Factory setting
Note: Be sure to set unused SW3-3 and 3-4 to OFF.
PC CONFIGURATOR
The following parameters can be set with using PC Configurator Software (model: R3CON):
•
0% scaling value
•
100% scaling value
•
0% adjustment value (bias)
•
100% adjustment value (gain)
•
0% input value
•
100% input value
•
Disable the unused channel