M-system R3-CZ4 Instruction Manual Download Page 2

R3-CZ4

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: 

+81(6)6659-8510  E-mail: info@m-system.co.jp

EM-8447  Rev.2  P. 2 / 3

COMPONENT IDENTIFICATION

ON

8

7

6

5

4

3

2

1

SW1

SW2

ON

8

7

6

5

4

3

2

1

SW3

ON

4

3

2

1

1

2

3

4

5

6

7

8

9

10

■ 

FRONT VIEW

 SIDE VIEW

ERR LED

RUN LED

Conv.

Rate

Input 2 (SW1)

  or

Input 4 (SW2)

Range

Input 1 (SW1)

  or

Input 3 (SW2)

Functions

 

STATUS INDICATOR LED

RUN indicator:

 Bi-color (red/green) LED; 

Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.

ERR indicator:

 Bi-color (red/green) LED; 

Red with the input abnormality;
Green in normal operating conditions.

 

SIDE DIP SW

• 

Input Range: SW1, SW2 

INPUT 1 (SW 1)

INPUT 2 (SW 1)

RANGE

INPUT 3 (SW 2)

INPUT 4 (SW 2)

1

2

3

4

5

6

7

8

OFF OFF OFF OFF OFF OFF OFF OFF 0 – 1.5mA (*)

ON OFF OFF OFF ON OFF OFF OFF 0 – 0.1mA

• 

Conversion Rate: SW3

SW

CONVERSION RATE

80 ms (

*

)

40 ms

20 ms

10 ms

SW3-1

OFF

ON

OFF

ON

SW3-2

OFF

OFF

ON

ON

(*) Factory setting
Note: Be sure to set unused SW3-3 and 3-4 to OFF.

PC CONFIGURATOR

The following parameters can be set with using PC Configurator Software (model: R3CON):

• 

0% scaling value

• 

100% scaling value

• 

0% adjustment value (bias)

• 

100% adjustment value (gain)

• 

0% input value

• 

100% input value

• 

Disable the unused channel

Reviews: