INPUT RANGE SELECTING

Select switches to match the input signal according to the table below.

SW311 SW305 SW304 SW303 SW302

SW405 SW404 SW403 SW402

SW301

O

N

2

1

3

4

5

6

7

8

SW702

SW702 is fixed to 
the position 3.
DO NOT CHANGE.

SW411

SW401 SW308 SW307 SW306

SW408 SW407 SW406

O

N

2

1

3

4

5

6

7

8

INPUT

SWITCHES

SETTING

NOTES

Thermocouple

SW301 – SW308  (ch 1 – ch 8)
SW401 – SW408  (ch 9 – ch 16)

Set to position “1”
                                

Attenuation OFF

SW311  (ch 1 – ch 8)
SW411  (ch 9 – ch 16)

OFF

Voltage input, 0.8V or less

SW301 – SW308  (ch 1 – ch 8)
SW401 – SW408  (ch 9 – ch 16)

Set to position “1”
                                

Attenuation OFF

SW311  (ch 1 – ch 8)
SW411  (ch 9 – ch 16)

ON

Voltage input, above 0.8V (*)

SW301 – SW308  (ch 1 – ch 8)
SW401 – SW408  (ch 9 – ch 16)

Set to position “3”
                                

Attenuation ON

SW311  (ch 1 – ch 8)
SW411  (ch 9 – ch 16)

ON

(*) Factory default setting

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input:  Check supply voltage.
3) Input:  Check that the input is within 0 – 100% of full-

scale.

4) DIP SW setting:  Check that all switches are set correctly.

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, please contact M-System’s Sales Office or repre-
sentatives.

Summary of Contents for R1M-GH

Page 1: ...r equivalent for the RS 232 C cable are recommended The equipment must be installed such that appropriate clearance and creepage distances are maintained to con form to CE requirements Failure to observe these re quirements may invalidate the CE conformance The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of this ...

Page 2: ... C port COM1 through COM5 supported LAN card LAN card by Windows 1 External e g SCSI devices may impair appropriate performance MSR128LS MSR128LV MSR128LS MSR128LV PC IBM PC AT or compatible Operating system Windows XP SP1 or SP2 For High Speed Mode Group 0 50 msec storing cycle use Windows XP SP1 SP2 Note Proper software functions may not be ensured under certain conditions CPU Pentium II 233 MHz...

Page 3: ...ok at the rear side on the DIN rail and push in the lower Push back the DIN rail adaptor WALL MOUNTING Set the body so that its DIN rail adaptor is at the bottom Pull down the DIN rail adaptor Refer to EXTERNAL DIMENSIONS TERMINAL CONNECTIONS Connect the unit as in the diagram below Attach the CJC sensor together with input wiring to the input screw terminals The sensor is calibrated for each part...

Page 4: ...ot designed to cancel noise included in the input signals Be careful to eliminate such noise by using shielded cables Note 2 Be sure to maintain the same potential at all the common negative terminals for DC input 9 8 7 6 5 4 3 2 1 10 12 11 13 15 14 16 17 18 20 19 21 22 23 24 25 27 26 28 29 30 31 32 33 35 34 36 TRIGGER INPUT T C INPUT DC INPUT INPUT 1 INPUT 2 INPUT 3 INPUT 4 INPUT 5 INPUT 6 INPUT ...

Page 5: ...re size 0 75 to 1 25 mm2 AWG19 to 16 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Nichifu Co ltd 6 max 24 3 12 max 3 2 13 dia mm inch EURO TYPE CONNECTOR TERMINAL Power input Modbus Applicable wire size 0 2 to 2 5 mm2 AWG24 to 12 Stripped length 7 mm COMMUNICATION CABLE CONNECTIONS R1M T1 T2 T3 T4 R1M T1 T2 T3 T4 T1 T2 T3 T4 R1M CONNECTOR RS 232 C RS 485 1 1 1 Internal terminating...

Page 6: ... 16 ON Voltage input above 0 8V SW301 SW308 ch 1 ch 8 SW401 SW408 ch 9 ch 16 Set to position 3 Attenuation ON SW311 ch 1 ch 8 SW411 ch 9 ch 16 ON Factory default setting CHECKING 1 Terminal wiring Check that all cables are correctly con nected according to the connection diagram 2 Power input Check supply voltage 3 Input Check that the input is within 0 100 of full scale 4 DIP SW setting Check tha...

Reviews: