R10M-CT4E

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-6247  P. 3 / 7

CONFIGURATOR SOFTWARE SETTING

The following parameters can be set with using PC Configurator Software (model: R10CFG)
Refer to the users manual for the R30CFG for detailed operation of the software program.

 

INPUT SETTING

Each channel can be set independently.

ITEM

SETTING RANGE

DEFAULT VALUE

Clamp-on Current Sensor

CLSE-R5 / CLSE-05 / CLSE-10 / CLSE-20 / CLSE-40 / CLSE-60

CLSE-R5

Zero Input

CLSE-R5: 0.000 - 5.000 (≤ full input)

0.000

CLSE-05: 0.00 - 50.00 (≤ full input)
CLSE-10: 0.00 - 100.00 (≤ full input)
CLSE-20: 0.00 - 200.00 (≤ full input)
CLSE-40: 0.00 - 400.00 (≤ full input)
CLSE-60: 0.00 - 600.00 (≤ full input)

Full Input

CLSE-R5: 0.000 - 5.000 (≥ zero input)

0.000

CLSE-05: 0.00 - 50.00 (≥ zero input)
CLSE-10: 0.00 - 100.00 (≥ zero input)
CLSE-20: 0.00 - 200.00 (≥ zero input)
CLSE-40: 0.00 - 400.00 (≥ zero input)
CLSE-60: 0.00 - 600.00 (≥ zero input)

Zero Fine Adjust

-320.00 - 320.00

0.00 (%)

Gain Zero Adjust

-3.2000 - 3.2000

1.0000

Zero Scaling

-32000 - 32000

0

Full Scaling

-32000 - 32000

10000

Cutout

0.0 - 5.0 (%)

1.0 (%)

 

MODBUS SETTING

ITEM

SETTING RANGE

DEFAULT SETTING

Data Mode

Modbus-RTU / Modbus-ASCII

Modbus-RTU

Address

1 - 247

1

Baud Rate

38400 / 19200 / 9600 / 4800 bps

38400 bps

Parity

None / Odd / Even

None

Communication timeout duration 0.1 - 3200.0 (sec.)

3.0 sec.

Depending on data mode and parity bit setting, data bit and stop bit are as following.

DATA MODE

PARITY BIT

DATA BIT

STOP BIT

Modbus-RTU

None

8

2

Odd or Even

8

1

Modbus-ASCII

None

7

2

Odd or Even

7

1

Summary of Contents for R10M-CT4E

Page 1: ...s connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system...

Page 2: ...during no Modbus communication Error ON Red Abnormality occurs in the unit i g memory failure OFF Normal status SD ON Green Sending data via RS 485 RD ON Green Receiving data via RS 485 TERMINAL ASSIG...

Page 3: ...t CLSE 40 0 00 400 00 full input CLSE 60 0 00 600 00 full input Full Input CLSE R5 0 000 5 000 zero input 0 000 CLSE 05 0 00 50 00 zero input CLSE 10 0 00 100 00 zero input CLSE 20 0 00 200 00 zero in...

Page 4: ...ARALLEL Mounting the unit A Hook the upper hook at the rear side of the base onto the DIN rail B Push the lower part of the unit in the direction of the arrow until the base is firmly fixed to the DIN...

Page 5: ...NSIONS unit mm inch DIN rail 35mm wide When mounting no extra space is needed between units 36 1 42 7 28 5 20 89 3 50 5 20 7 28 72 2 83 80 3 15 45 1 77 4 16 CONNECTION DIAGRAM 1 6 2 7 3 8 4 9 Jack 12...

Page 6: ...SLD FE TERMINATOR TERMINATOR Note The terminator must be connected across DA and DB at both ends of communication line WIRING COMMUNICATION WITH HOST PC MODBUS I O MODULE WIRING INSTRUCTIONS FOR BASE...

Page 7: ...ge error Input Register 3X 1 I Analog Input analog input 1 2 I Analog Input analog input 2 3 I Analog Input analog input 3 4 I Analog Input analog input 4 Note DO NOT access addresses other than the o...

Reviews: