LINEARIZATION TABLE

Max. 32 calibration points defined by sets of input and output values can be programmed.  Use only necessary number of 
points, arranged in order from the smallest input value.

-15%

0

X01

X02

X03

X04

X05 +115%

Y01

Y02

Y03

Y04

+100%  Y05

INPUT

OUTPUT

-5%

START

COMPLETE

Go to the PROGRAM mode

Go to the MONITOR mode

Create Linearization Table

• Set the 1st calibration point (input & output) to ITEM 21/22
• Set the 2nd calibration point (input & output) to ITEM 23/24
[e.g.] Set the 2nd input point to 50.0%, output point to 20.0%
• Press ITEM     or     key until the display shows ITEM 23
• Press DATA     or     key until the DATA display shows 50.0
• Press ITEM     or     key until the display shows ITEM 24
• Press DATA     or     key until the DATA display shows 20.0

Enable Linearization Table
• Press ITEM     or     key until the display 
  shows ITEM 20
• Press DATA     or     key until the display 
  shows DATA 1

Disable Linearization Table

• Press ITEM     or     key until the display 
  shows ITEM 20.
• Press DATA     or     key until the display 
  shows DATA 0.

Need Linearization?

YES

NO

Summary of Contents for MXS

Page 1: ...ient ventilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 5 to 55 C 23 to 131 F with re...

Page 2: ...al conditioner output will be shifted by 180 3 OUTPUT 4 5 1 2 U V POWER 7 8 S3 S2 S1 R1 R2 SELF SYNCH FRONT PANEL CONFIGURATION PROGRAMMING PROGRAMMING PROCEDURE 1 Press ITEM UP or DOWN key until ITEM...

Page 3: ...rage sampling cycle 150 msec 0 No 1 4 samples 2 8 samples 3 16 samples 4 32 samples 0 14 2 0 1 60 Power saving mode 0 Continuous display 1 60 Time before display turned off minutes 10 15 16 2 2 15 0 0...

Page 4: ...y shows 270 0 0 1 increments 0 Input Angle Position Setting 1 Fix the self synch motor to the desired 0 position Press ITEM or key until the display shows ITEM 03 Press DATA key to show DATA 1 and dou...

Page 5: ...play shows 10 0 Deviation from the absolute 0 Shift 0 input SELECTING OUTPUT RANGE Example Output range 10 0 to 0 0V START COMPLETE Go to the PROGRAM mode Go to the MONITOR mode 0 Output Press ITEM or...

Page 6: ...Linearization Table Set the 1st calibration point input output to ITEM 21 22 Set the 2nd calibration point input output to ITEM 23 24 e g Set the 2nd input point to 50 0 output point to 20 0 Press ITE...

Page 7: ...rminal wiring Check that all cables are correctly con nected according to the connection diagram 2 Input signal and power input voltage Check wiring across MXS and self synch as follows terminal 3 S1...

Reviews: