FRONT VIEW & PROGRAMMING

 PROGRAMMING PROCEDURE

1)  Press ITEM UP or DOWN key until ITEM display indicates “01”.
2)  Press DATA UP or DOWN key and choose “2” on DATA display.
   

1  : Data indication only.

   

2  : All parameters are modifiable.

3)  Press  ITEM  UP  or  DOWN  key  until  ITEM  display  shows  the 

ITEM No. you need to change.

4)  Press DATA UP or DOWN key and choose a DATA No. or value 

you need on DATA display.

5)  Repeat  above  3  and  4.    (Entered  data  is  stored  1  sec.  after  the 

operation has been complete.)

6)  Press ITEM UP or DOWN key until ITEM display indicates “01”.
7)  Press DATA UP or DOWN key and choose “1” on the display.
8)  Press ITEM UP or DOWN key until ITEM display indicates “P”.  

DATA display shows process input.  You can now check data set

-

ting by choosing ITEM No.

Note : DO NOT press UP and DOWN keys simultaneously.

PL4

PL3

PL2

PL1

DATA

ITEM

DATA

ITEM

ITEM No. Display

DATA UP-DOWN Keys

ITEM No. UP-DOWN Keys

DATA Display

DOWN LED

UP LED

STOP LED

Polarity LED

 

ITEM  

MDF.

 

DATA 

CONTENTS 

    

DEFAULT

  

CODE

 

  P 

N/A 

-9999 – 9999 

Input display in engineering unit (as set in ITEM 08/09) 

---

  01 

 

1, 2, 3 

Modification code 

1  : Data indication only. 

1

 

 

 

 

 

2  : All parameters are modifiable.

 

 

 

 

 

3  : Only ITEM 33 is modifiable.

  02 

N/A 

0, 1, 10, 20 

Status indication (“0” is normally indicated.) 

---

 

 

 

 

 

0  : Normal

 

 

 

 

 

1  : E

2

PROM error

 

 

 

 

 

10 : PV overrange (out of -9999 to 9999)

 

 

 

 

 

20 : Output overrange 

 

 

 

 

 

       (out of -15 to 115% or between item 31 and 32)

  03/L 

-15.0 – 115.0 

Input indicated in % with ITEM 01 DATA 1 (of the range set in ITEM 27/28) 

---

 

 

 

 

Loop test output with ITEM 01 DATA 2 (‘L’ is indicated as ITEM No.)

 

 

 

 

(Use DATA UP/DOWN key to set the output signal.)

  04 

-99.99 – 99.99  Input zero adjustment (%) (fine adj. of the value set in ITEM 27) 

0.00

  05 

-99.99 – 99.99  Input span adjustment (%) (fine adj. of the value set in ITEM 28) 

0.00

  06 

-99.99 – 99.99  Output zero adjustment (%) (fine adj. of the value set in ITEM 29) 

0.00

  07 

-99.99 – 99.99  Output span adjustment (%) (fine adj. of the value set in ITEM 30) 

0.00

  08 

-9999 – 9999 

Display range scaling     0% *

1

 0.0

  09 

-9999 – 9999 

Display range scaling 100% *

1

 100.0

  10 

0, 1, 2, 3 

Decimal point position  0  : _ _ _ _ 

1

 

 

 

 

 

1  :  _ _ _ . _

 

 

 

 

 

2  : _ _ . _ _

 

 

 

 

 

3  :  _ . _ _ _

  11 

0, 1, 2, 3, 4, 5 

Moving average (sampling cycle: 10 msec.) 

1

 

 

 

 

0: No   1: 5 samples   2: 8 samples   3: 12 samples   4: 20 samples   5: 36 samples

  12 

0 – 12 

Response time 

12 : Approx. 100 sec. (0 – 90%) 

1

 

 

 

 

Decreasing DATA by 1 increment cuts the response time by half.

  13 

0, 1 

MANUAL control mode      

0

 

 

 

 

0 : Trace back mode; Goes back the preset ‘trace-back time’

 

 

 

 

1 : Fixed value mode; Holds the preset ‘initial value in MANUAL mode’

  14 

-15.0 – 115.0 

Initial value in MANUAL mode 

-15.0

  15 

0 – 20 

Trace-back time (sec.) 

    

0

  16 

0, 1 – 100 

Transition speed (%/sec.)     

0

 

 

 

 

(For tracking the new input when switched from MANUAL to AUTO mode)

 

 

 

 

0 : CAS operation is restored without going through the transition response 

 

 

 

 

     when MAN command is OFF.

  17 

0, 1 

Output stored at the loss of power 

1

 

 

 

 

0 : Disable     1 : Enable

  18 

-15.0 – 115.0 

Initial value at start-up      

-15.0

 

 

 

 

(Effective when ‘Output stored at the loss of power’ is disabled.)

  19 

1 – 999 

UP-DOWN key response time (0 – 100%, sec.) 

20

  20 

0, 1 

Transition response time     

0

 

 

 

 

0 : 

Disable; Response is determined only by UP/DOWN key response time setting.

 

 

 

 

1 : Enable; Response increases gradually from 0% to the UP-DOWN key 

 

 

 

 

     response time setting.