MSP4 / MSP5 / MSP6

P.  / 7

EM-4854 Rev.8

MINI-TOP ELECTRONIC ACTUATOR

(linear type)

MODEL

MSP4/MSP5

/MSP6

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If  you  have  any  problems  or  questions  with  the  product, 
please contact M-System’s Sales Office or representatives.

 PACKAGE INCLUDES:

  Mini-Top ........................................................................ (1)
    2.5 mm Hexagon key wrench (with option /S) ............ (1)

The Mini-Top is not provided with a yoke or other compo-
nents required for mounting it to a valve.  They are to be 
provided by the user.

 MODEL NO.

Confirm  Model  No.  marking  on  the  product  to  be  exactly 
what you ordered.

POINTS OF CAUTION

 CONFORMITY WITH EC DIRECTIVES

• This equipment is suitable for use in a Pollution Degree 

2 environment and in Measurement Category II, with the 
maximum  switching  voltage  of  125V.  (Applicable  to  the 
full-open/-closed signal only)

  Prior to installation, check that the insulation class of this 

unit satisfies the system requirements.

• Altitude up to 2000 meters
• The  equipment  must  be  installed  such  that  appropriate 

clearance and creepage distances are maintained to con-
form  to  CE  requirements.    Failure  to  observe  these  re-
quirements may invalidate the CE conformance.

• Install  lightning  surge  protectors  for  those  wires  con-

nected to remote location.  Refer to “LIGHTNING SURGE 
PROTECTION” section below.

 POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

  Rating 100 – 120V AC: 90 – 132V, 47 – 66 Hz, approx. 25VA
  Rating 200 – 240V AC: 180 – 264V, 47 – 66 Hz, approx. 25VA
  Rating 24V DC: 24V ±10%, approx. 0.6A
• A  fuse  of  the  following  rating  is  incorporated:  250V/1A 

time delay.

• A rush current 1.5 times as high as the above ratings can 

flow at the startup.

 GENERAL PRECAUTIONS

• Remove the power supply to the actuator before wiring to it.

 INSTALLATION

• Indoor, or outdoor where the MSP is NOT exposed to di-

rect sunlight

• Ambient temperature:  -5 to +55°C (23 to 131°F)
• Operating humidity 30 to 85% RH (non-condensing)
• Vibration: 0.5 G max.
• Install  the  MSP  where  you  can  reach  for  maintenance.  

Observe  at  the  minimum  of  15  centimeters  (6  inches) 
above the cover.

 OUTDOOR USE

• When installing the MSP outdoor or where it is exposed to 

rain or water drops, be sure to fasten the cable connector 
tightly and leave a slack of the cable.

• Do not mount the MSP in such direction that the output 

stem or cable connector is at the top of the MSP unit.

 ELECTRICAL CONNECTION

• With DC power type unit, power supply and signal lines 

are not isolated.  Use an isolator if needed.

• When  you  use  a  cable  other  than  the  standard  1-meter 

cable  equipped  with  non-terminal  box  type  unit  and  its 
extension distance is longer than that, use shielded cables 
for signal line, or install signal cables in a separate piping 
from power supply cables.

 LIGHTNING SURGE PROTECTION

• In order to protect the unit from lightning surges entering 

through cables, use of appropriate lightning surge protec-
tors  are  recommended.    For  24V  DC  power  supply  line, 
choose a surge protector with its maximum surge voltage 
40V or less between lines.  Recommended M-System mod-
el: MDP-D24.

 PID CONTROLLER

• Choose PID parameters carefully so that the MV remains 

as stable as possible.  Unstable operations shorten the life 
of actuator and valve.

 O-RING, GASKET

• When  replacing  the  actuator  cover  after  adjustments, 

check that the O-ring is securely placed in the groove. 

• When  replacing  the  terminal  box  cover,  check  that  the 

gasket is in place.

 YOKE DESIGN

• When a foreign object is caught in the valve, a thrust 2 

times greater than the maximum rating could be gener-
ated.  Leave enough strength for mechanical components 
such like the yoke and stem.

• If the MSP is used on a steam line in temperature control, 

it is possible that the MSP’s temperature rises higher than 
the ambient temperature due to transmission or radiation 
via the steam piping, even when the ambient temperature 
is within allowable range.

  Use a longer yoke to increase heat dissipation and apply 

insulating material.

 AND ....

• DO NOT loosen the screw fixing the potentiometer stem.  

Loosening it could cause a malfunction.

• DO NOT step onto the actuator.  DO NOT rest a heavy 

object on or against it.

Cable Connector

DO NOT Pull Tightly

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for MSP5

Page 1: ...emale thread 1 0 pitch 1 M10 female thread 1 25 pitch D M6 female thread 1 0 pitch E M8 female thread 1 25 pitch F M10 female thread 1 5 pitch 4 SEQUENTIAL CONTROL SIGNALS L Full open closed signal F Forced open close signal B Full open closed and forced open close signals Select With Terminal Box 0 Without 5 TERMINAL BOX T With 0 Without 6 INPUT Current A 4 20 mA DC Input resistance 250 Ω Z Speci...

Page 2: ...0 mm 300 N 67 lbs MSP5 x7 18 sec 10 mm 700 N 157 lbs Position Output 1 5 V DC not isolated With direct action 5 1 V DC position output is provided proportionally to 4 20 mA DC 1 5 V DC input Load resistance 5 kΩ Full open closed signals Limit switch contact Rating 125 V AC 0 75 A cos ø 1 30 V DC 0 6 A resistive load Mechanical life 3 10 7 cycles Maximum operation frequency 60 cycles min INSTALLATI...

Page 3: ...or above 100 Limiters are set at approx 1 5 for the full closed side approx 101 5 for the full open side Seal Spring The Mini top Series incorporates a seal spring to maintain the sealing pressure when the valve is fully closed The standard spring has 0 5 1 mm 02 04 flexibility to facilitate the full closed adjustment TERMINAL CONNECTIONS black 1 U V COM1 COM2 COM1 white 2 red 3 green 4 yellow 5 b...

Page 4: ... M10 1 25 15 D M 6 1 0 E M 8 1 25 F M10 1 5 42 1 65 43 1 69 67 2 64 85 3 35 34 1 34 141 5 55 181 7 13 90 3 54 130 5 12 98 3 86 50 1 97 max 46 1 81 dia 4 M5 10 39 deep 31 1 22 2 08 36 0 1 dia 0 66 2 60 dia M See the table to the right YOKE CONNECTION for AC power supply 40 1 57 max with 5 10 mm stroke YOKE SURFACE 20 79 60 2 36 35 1 38 7 5 30 2 G 1 2 CONDUIT 32 5 1 28 Cable connector or leadwires n...

Page 5: ...COM2 FULL OPEN or FULL CLOSED SIGNAL POSITION OUTPUT 1 5V DC POWER MODE SELECTOR POWER INPUT STATUS POT MOTOR LIMIT SW Full open closed signals and forced open close signals are optional Disregard the switching regulator circuit for DC power input Specifications are subject to change without notice Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com ww...

Page 6: ...ce Observe at the minimum of 15 centimeters 6 inches above the cover OUTDOOR USE When installing the MSP outdoor or where it is exposed to rain or water drops be sure to fasten the cable connector tightly and leave a slack of the cable Do not mount the MSP in such direction that the output stem or cable connector is at the top of the MSP unit ELECTRICAL CONNECTION With DC power type unit power sup...

Page 7: ... new fuse is melted again soon after it has been re placed there may be problems with the control PCB or the motor Contact M System or sales representative RE STARTING TIMER The MSP is equipped with a timer circuit which gives an interval period 0 10 sec between stop restart actions to prevent the motor and other internal components from overheating It is recommended to set a long restarting time ...

Page 8: ...n Clockwise Adjustable Zero Range Adjustable Span Range Figure 4 I O Characteristics Adjustable Range Table 1 Available Stroke Range for Each Model MODEL L MIN STROKE MAX STROKE MSP4 1 29 5 10 MSP4 2 34 8 15 MSP5 1 40 5 10 MSP5 3 50 10 20 MSP6 3 58 10 20 MSP6 4 78 20 40 Figure 5 Minimum Maximum Stroke Maximum Stroke Minimum Stroke L Yoke Surface MANUAL OPERATION FUNCTION for MSP4 AC power supply 1...

Page 9: ...P Mounted to a Valve Remark 1 The yellow wire must be left unconnected if the position output signal is not required Cut the exposed section of copper wire and insulate the tip of the wire Remark 2 The MSP6 is not provided with full open closed signals black 1 U V COM1 COM2 COM1 white 2 red 3 green 4 yellow 5 blue 6 gray 7 brown 8 1 to 8 Terminal No of terminal box Full open closed signals and for...

Page 10: ...ol PCB as shown in Figure 3 Other adjustments which are paint locked are for factory use only and should be changed only by qualified M System personnel M System is not liable for any malfunction or inconvenience caused by unauthorized change of them by the user DIRECT REVERSE ACTION The actuator action is factory set to Reverse the output stem is retracted with an input signal increase and the op...

Page 11: ...l sound No abnormal sound is heard during operation Repair or calibration Connector Leadwire The connector is firmly connected No breakdown of leadwires The insulation covers are not torn not bruised Repair or calibration Inside humidity rust No condensation No rust If there is water inside check the packing Remove water dry the case and inside parts Replace rusted parts Calibration If the packing...

Page 12: ...pply voltage Check the power supply Fuse melted Replace the fuse ON ON Malfunction by noise Turn off the power supply and restart Low power voltage or insufficient capacity Check the power supply ON OFF Malfunction by noise Turn off the power supply and restart Low power voltage or insufficient capacity Check the power supply Unstable functioning Power voltage is low or fluctuating Check the power...

Reviews: