MODEL: MRP4

Final Control Elements

MINI-TOP ELECTRONIC ACTUATOR

(rotary type)
Functions & Features
• Small-size control valve actuator
• Electrical positioner incorporated
• 1/1000 high resolution
• Easy adjustment: electronic limiter at the valve open &
closed positions
• Overload protection
• Various power inputs
• CE marking available for 24 V DC power

Typical Applications
• Actuator for automatic control valve in pilotplants
• Air-conditioning in buildings or plants
• Micro-flow control for pharmaceutical injection
• For small-size control valves

MODEL: MRP4–[1][2][3][4]–[5][6][7]

ORDERING INFORMATION

• Code number: MRP4-[1][2][3][4]-[5][6][7]
Specify a code from below for each [1] through [7].
(e.g. MRP4-14LT-A0R)
• Special input range (for codes Z and 0)

[1] SPAN

1: 45 to 90 degrees
2: 90 to 180 degrees

[2] OPERATION TIME, TORQUE

4: 7 seconds / 90°, 5 N·m
5: 13 seconds / 90°, 5 N·m

[3] SEQUENTIAL CONTROL SIGNALS

L: Full-open/-closed signal
F: Forced open/close signal
B: Full-open/-closed and forced open/close signals

(Select 'With Terminal Box.')
E: Full-closed/overload signal (Not selectable for CE)
0: Without

[4] TERMINAL BOX

T: With
0: Without

[5] INPUT

Current

A: 4 – 20 mA DC (Input resistance 250 Ω)
Z: Specify current (See INPUT SPECIFICATIONS)

Voltage

6: 1 – 5 V DC (Input resistance approx. 1 MΩ)
0: Specify voltage (See INPUT SPECIFICATIONS)

[6] CE MARKING

C: With
0: Without

[7] POWER INPUT

AC Power

K3: 100 – 120 V AC
(Operational voltage range 90 – 132 V, 47 – 66 Hz)
 (Not selectable for CE)
L3: 200 – 240 V AC
(Operational voltage range 180 – 264 V, 47 – 66 Hz)
  (Not selectable for CE)

DC Power

R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

GENERAL SPECIFICATIONS

Degree of protection: IP55
Action: Direct or reverse; field selectable with DIP switches
(factory set to “reverse”)
(In “reverse” action, the output stem seen from the cover
turns counterclockwise with an input signal increase.)
Operation at abnormally low input: Counterclockwise turn,
clockwise turn or stop; field selectable with DIP switches
(factory set to“clockwise”)
Note: Counterclockwise or clockwise if seen from the cover.
Detectable input drop level: -16 ±2.5 %
Electrical connection
•No terminal box
 Wiring conduit: G 1/2 female; cable connector with 1 meter
wire (0.5 mm

2

) provided

•Terminal box
 Wiring conduit: G 1/2 female (two)
 Terminal screws: M3 pillar terminal

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for MRP4

Page 1: ...t A 4 20 mA DC Input resistance 250 Z Specify current See INPUT SPECIFICATIONS Voltage 6 1 5 V DC Input resistance approx 1 M 0 Specify voltage See INPUT SPECIFICATIONS 6 CE MARKING C With 0 Without 7...

Page 2: ...n frequency 60 cycles min Full closed overload signal Relay contact Full closed signal trips at approx 2 of span Rating 250 V AC 1 A cos 1 30 V DC 1 A resistive load INSTALLATION Power Consumption AC...

Page 3: ...ic limiters in order to prevent mechanical locks when the input goes below 0 or above 100 Limiters are set at approx 0 5 for the full closed side approx 100 5 for the full open side Full open closed s...

Page 4: ...3 2 4 6 5 7 8 11 9 10 With Both Full open closed Signal and Forced Open Close Signal COM2 COM1 COM3 POWER black 1 U V white 2 red 3 INPUT COM1 green 4 POSITION OUTPUT 1 5V DC yellow 5 blue 6 gray 7 b...

Page 5: ...4 23 91 42 1 65 43 1 69 35 1 38 60 2 36 110 4 33 150 5 91 98 3 86 90 3 54 130 5 12 2 08 127 5 167 6 57 17 67 10 0 043 sq 0 46 1 81 dia 4 M5 10 39 deep 2 G 1 2 CONDUIT YOKE SURFACE 36 0 1 dia 0 12 47 d...

Page 6: ...CW CW RESTART TIMER DEADBAND ADJ MODE SELECTOR Motor Control Logic Motor Driver Hi Lo Limiter Input Circuit Position Output Switching Regulator POWER Power Circuit CCW CW FORCED OPEN CLOSE SIGNAL POWE...

Page 7: ...ters 6 inches above the cover OUTDOOR USE When installing the MRP outdoor or where it is exposed to rain or water drops be sure to fasten the cable connector tightly and leave a slack of the cable Do...

Page 8: ...life of the actuator FUSE A fuse is equipped for protection against overload current When you turn the power supply on check that the power LED is on If it is off check that the fuse is melted Replace...

Page 9: ...rse Actions Operation at Abnormally Low Input Power Indicator green with power supplied Input Indicator green with input applied Status Indicator red blinks in 2 sec intervals blinks in 0 5 sec interv...

Page 10: ...L MIN SPAN MAX SPAN MRP4 1 MRP5 1 45 90 MRP6 1 MRP4 2 90 180 MRP6 2 Standard Zero Position M i n i m u m s p a n M a x i m u m s p a n M a x i m u m O p e r a t i o n R a n g e 5 d e g 5 d e g Adjusta...

Page 11: ...nal COM2 COM1 COM2 POWER black 1 U V white 2 red 3 INPUT COM1 green 4 POSITION OUTPUT 1 5V DC yellow 5 blue 6 gray 7 brown 8 FULL OPEN or FULL CLOSED SIGNAL output stem turned CCW output stem turned C...

Page 12: ...The following explanation applies to reverse action For di rect action read the value in the brackets Remark Applying an over torque to the adjustments may destroy stoppers or other sections of them U...

Page 13: ...nd Check input signal Narrow the deadband ON Flash 0 5 sec Actuator mechanism is damaged Repair Overload cause by a foreign object caught in the valve Check the valve Control PCB damaged Repair or rep...