background image

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Lightning surge protector ...................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTALLATION / INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, and basic main-
tenance procedure.

LIMITATION APPLICABLE TO M-RESTER

The M-RESTER will protect electronics equipment from 
damage caused by lightning by absorbing most of the 
surge voltages.
However, M-RESTER may not be effective against cer-
tain extremely high voltages caused by a direct or almost 
direct hit by lightning.
M-RESTER must be installed according to this installa-
tion / instruction manual.

GENERAL

 

FUNCTION & FEATURES

• Designed specifically for AC power supplies up to 10 amps
• Discharge current capacity 10000A
• Absorbs surges only without affecting instrumentation 

signal

• Indicator LED turns off with surge absorber anomaly
• Fuse provided for preventing ignition caused by failure of 

surge absorber

 

SPECIFICATIONS

BETWEEN LINES

LINE TO 

GND

MMA-100

 MMA-200

Discharge voltage

190V min.

410V min.  680V min.

Max. surge voltage*

350V max.  700V max. 800V max.

Leakage current 

≤4mA

@150V DC

≤4mA

 @300V DC

≤0.1mA

@300V DC

Response time

≤0.01 µsec.

Discharge current

10000A (8 / 20 µsec.)

Max. load current

10A

Internal series resist.

≤0.5Ω including return

*The maximum voltage that could pass through M-RESTER. 
Protected equipment must be able to withstand this voltage 
for a very short time period.

POINTS OF CAUTION

 

ENVIRONMENT

• When heavy dust or metal particles are present in the at-

mosphere, install M-RESTER inside proper housing and 
ventilate it.

• Do not install the M-RESTER where it is subjected to 

continuous vibration. Do not apply physical impact to the 
M-RESTER.

• Environmental temperature must be within -5 to +55°C 

in order to ensure adequate life span and operation.

 

WIRING

• The discharge element incoporated in the M-RESTER is 

grounded to its housing. Therefore, DO NOT do an insu-
lation test. If you do, the element will start discharging 
between line and ground at the discharge voltage value.

 

RATED CURRENT

• Be sure that the rated current of protected equipment 

does not exceed the maximum load current specification 
of the M-RESTER.

• Be sure to install a breaker which matches the current 

rating at the power source side of the M-RESTER.

 

AND ....

• We recommend that you keep spare M-RESTERs so that 

you can replace them when necessary

COMPONENT IDENTIFICATION

U

V

G

Terminals,

Protected Equipment Side

Body

Specification

Label

Terminals,

Cable Side

Alarm Indicator LED

 

FRONT PANEL CONFIGURATION

U

V

G

u

v

SURGE

SIDE

PROTECT

SIDE

ALM

LIGHTNING SURGE PROTECTOR FOR POWER SUPPLY USE

(10A; high discharge current capacity)

MODEL

MMA

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8173  Rev.5  P. 1 / 3

INSTRUCTION MANUAL