background image

MODEL: M2LMS

(110 V ±10 % for UL)

[4] OPTIONS (multiple selections)

STANDARDS & APPROVALS (must be specified)

/N: Without CE or UL
/CE: CE marking
/UL: UL approval (CE marking)

OTHER OPTIONS

blank: none
/Q:  Option other than the above (specify the specification)
(UL not available)

SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)

/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

TERMINAL SCREW MATERIAL

/S01: Stainless steel

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection: M3 screw terminals (torque 0.8 N·m)
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Overrange output: Approx. -10 to +105 % at 1 – 5 V
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
Limit adjustments: High and low independently adjustable
from -10.0 – +105 %; 0.1 % increments (1 % increments
over 100 %)
High/low selector: Double-throw SW (front)
UP/DOWN control: Double-throw, momentary SW (front)
■ INDICATORS
High/low digital display: Red LED; 6.4 mm (.25”) 7 segment,
3 digits
Polarity indicator: Dual color (red/green) LED; Red with a
positive set value; Green with a negative set value.
Power saving mode: Indicators turn off if the switches are
untouched for 1 minute.

INPUT SPECIFICATIONS

• DC Current:
Shunt resistor attached to the input terminals (0.5 W)
Specify input resistance value for code Z.
• DC Voltage: -30 – +30 V DC
Minimum span: 3 mV
Offset: Max. 1.5 times span
Input resistance
Span 3 – 10 mV : ≥ 10 kΩ

Span 10 – 100 mV : ≥ 10 kΩ
Span 0.1 – 1 V : ≥ 100 kΩ
Span ≥ 1 V : ≥ 1 MΩ

OUTPUT SPECIFICATIONS

• DC Current: 0 – 20 mA DC
Minimum span: 1 mA
Offset: Max. 1.5 times span
Load resistance: Output drive 15 V max.
• DC Voltage: -10 – +12 V DC
Minimum span: 5 mV
Offset: Max. 1.5 times span
Load resistance: Output drive 1 mA max.; at ≥ 0.5 V

INSTALLATION

Power Consumption
•AC Power input:
 Approx. 3 VA at 100 V
 Approx. 4 VA at 200 V
 Approx. 5 VA at 264 V
•DC Power input: Approx. 3 W
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 150 g (0.33 lbs)

PERFORMANCE in percentage of span

Accuracy: ±0.2 %
Setting accuracy: ±0.2 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute  (input to output
to power to ground)

STANDARDS & APPROVALS

CE conformity:
  EMC Directive (2004/108/EC)
  EN 61000-6-4 (EMI)
  EN 61000-6-2 (EMS)
  Low Voltage Directive (2006/95/EC)
  EN 61010-1
  Installation Category II
  Pollution Degree 2
  Max. operating voltage 300 V
  Input or output to power: Reinforced insulation
  Input to output: Basic insulation
Approval:
  UL/C-UL nonincendive Class I, Division 2,

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for Mini-M Series

Page 1: ...k min 16 0 60 mV DC Input resistance 10 k min 2 0 100 mV DC Input resistance 100 k min 3 0 1 V DC Input resistance 1 M min 4 0 10 V DC Input resistance 1 M min 5 0 5 V DC Input resistance 1 M min 6 1...

Page 2: ...nput resistance value for code Z DC Voltage 30 30 V DC Minimum span 3 mV Offset Max 1 5 times span Input resistance Span 3 10 mV 10 k Span 10 100 mV 10 k Span 0 1 1 V 100 k Span 1 V 1 M OUTPUT SPECIFI...

Page 3: ...hen the set value is in positive range green when in negative range The high limit is factory set to 100 How to Set Low Limit Turn the High Low Limit Selector C to the bottom The High Low Limit Displa...

Page 4: ...Z 1 Low Drift Amplifier Output Driver OUTPUT 4 5 8 9 12 U V POWER 13 14 Input shunt resistor attached for current input INPUT R Digital Computation UP DOWN SW HI LO LIMIT SELECTOR Hi Lo Limit Display...

Page 5: ...must be mounted inside a panel The equipment must be installed such that appropriate clearance and creepage distances are maintained to con form to CE UL requirements Failure to observe these re quire...

Page 6: ...ta sheet When the output is out of tolerance recalibrate the unit according to the ADJUST MENT PROCEDURE explained earlier FRONT PANEL CONFIGURATION How to Set High Limit Turn the High Low Limit Selec...

Page 7: ...70 5 2 78 86 7 3 41 7 3 29 15 59 6 23 59 2 32 DIN RAIL 35mm wide 4 16 8 M3 SCREW 72 2 83 23 91 2 4 2x5 17x 20 MTG HOLE 6 24 deep 116 7 4 59 When mounting no extra space is needed between units 1 4 8...