WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.8 N·m

 

SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG.Co.Ltd, Nichifu Co.,ltd

6 (.24) max

3.3 (.13) max

mm (inch)

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2)  Input range selector:  Check that the switch is at the ap-

propriate position according to the input range model 

suffix code.

3) Power input voltage:  Check voltage across the terminal 

13 – 14 with a multimeter.

4) Input:  Check that the input wires are correctly connect-

ed to the input terminals according to the selected input 

type.

5) Output:  Check that the load resistance meets the de-

scribed specifications.

6) Status indicator LED:  Check that it blinks in a regular 

pattern.

HARDWARE ADJUSTMENTS

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, fine zero and span adjustments can 
be done to ±5% by pressing UP/DOWN switches enabled 
with the zero/span selector switch.  Calibrated values are 
stored in the non-volatile memory, which will not be lost 
even when you turn off power supply to the unit.
Zero and span are respectively set to 0% and 100% at the 
factory.

UP/DOWN Switches

The front cover cannot be opened to 180 deg. 

when flush with neighboring units.

Configurator Jack

■ 

FRONT VIEW (with cover open)

■ 

RIGHT SIDE VIEW

Status Indicator LED

Zero/Span Selector

Top: SPAN

Middle: OFF

Bottom: ZERO

Input Range Selector

Position H

Position L

: code S2, Z1

: other

Zero/Span Selector

 

ZERO

:   UP/DOWN switches usable for zero adjustment.

 

OFF

:   UP/DOWN switches unavailable.

 

SPAN

:   UP/DOWN switches usable for span adjustment.

UP/DOWN Switches

(Incrementing speed will be doubled when the switch is 
held down.)
 

UP

:    

Pressing UP increases adjusted values.

 

DOWN

:  Pressing DOWN decreases adjusted values.

 

HOW TO RESET

You can reset manually calibrated zero and span to their ex-
factory state by pressing both UP/DOWN switches at once.

 

HOW TO CALIBRATE ZERO/SPAN

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 20 minutes.

1) ZERO:  Apply 0% input.  Slide the Zero/Span Selector to 

the bottom position.  Press the UP or DOWN switches 

and adjust output to 0%.

2) SPAN:  Apply 100% input.  Slide the Zero/Span Selector 

to the top position.  Press the UP or DOWN switches and 

adjust output to 100%.

3) Check ZERO adjustment again with 0% input.
4) The ZERO and SPAN adjustments are processed in a 

digital processor, and therefore do not interact.  However, 

if ZERO value is changed, repeat the above procedure 1) 

– 3).

 

HOW TO CANCEL RESISTANCE IMBALANCES BETWEEN 

RTD LEADWIRES

Resistance imbalances between RTD leadwires can be can-
celled by manipulating the Zero/Span Selector and UP/
DOWN switches.

1) Press and hold down the DOWN switch.  Switch the 

Zero/Span Selector to the bottom position and release 

the DOWN switch.  Check that the status indicator LED 

which was blinking has turned ON.

2) Press the DOWN switch once and release to cancel any 

resistance imbalances.

3) Return the Zero/Span Selector to the middle position.  

The status indicator LED will start blinking again.

 

HOW TO CAPTURE THE POTENTIOMETER’S ZERO/SPAN

Particular positions of the potentiometer can be captured 
(stored in memory) as ZERO (0%) or SPAN (100%) points by 
manipulating Zero/Span Selector and UP/DOWN switches.

ZERO

1) Press and hold down the DOWN switch.  Switch the 

Zero/Span Selector to the bottom position and release 

the DOWN switch.  Check that the status indicator LED 

which was blinking has turned ON.

2) Press the DOWN switch once and release to capture zero.
3) Return the Zero/Span Selector to the middle position.  

The status indicator LED will start blinking again.

SPAN

1) Press and hold down the DOWN switch.  Switch the Zero/

Span Selector to the top position and release the DOWN 

switch.  Check that the status indicator LED which was 

blinking has turned ON.

2) Press the DOWN switch once and release to capture 

span.

3) Return the Zero/Span Selector to the middle position.  

The status indicator LED will start blinking again.