background image

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5062  Rev.8  P. 1 / 4

INSTRUCTION MANUAL

Mini-M

THERMOCOUPLE TRANSMITTER

(PC programmable)

MODEL

M2XT2

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Signal conditioner (body + base  CJC sensor) .....(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.
The unit is programmable using the PC Configurator Soft-
ware.  For detailed information on the PC configuration, 
refer to the JXCON users manual.  The JXCON PC Con-
figurator Software is downloadable at M-System’s web site: 
http://www.m-system.co.jp

POINTS OF CAUTION

 

NONINCENDIVE APPROVAL OPTION

• This equipment is suitable for use in Class I, Div. 2, 

Groups A, B, C and D or Non-Hazardous Locations only.

• 

WARNING!

 Before You Remove the Unit from Its Base 

Socket or Mount It, Turn Off the Power Supply and Input 
Signal for Safety.

• 

WARNING!  – Explosion Hazard –

 

 

Substitution of Components May Impair Suitability for 
Class I, Div. 2.

• 

WARNING!  – Explosion Hazard –

 

 

Do Not Disconnect Equipment Unless Power Has Been 
Switched Off or The Area is Known To Be Non-Hazardous.

• The equipment was evaluated for use in the ambient tem-

perature and relative humidity as mentioned in ‘ENVI-
RONMENT’ section.

• The input and output wiring must be in accordance with 

Class I, Div. 2 wiring methods and in accordance with the 
authority having jurisdiction for use in these hazardous 
locations.

 

CONFORMITY WITH EU DIRECTIVES, UK LEGISLATION OR UL

• This equipment is suitable for Pollution Degree 2 and In-

stallation Category II (transient voltage 2500V).  Rein-
forced insulation (signal input or output to power input: 
300V) and basic insulation (signal input to output: 300V) 
are maintained.  Prior to installation, check that the insu-
lation class of this unit satisfies the system requirements.

• The equipment must be mounted inside a suitable fire 

enclosure.

• Altitude up to 2000 meters.
• The equipment must be mounted inside a panel.
• Risk of Electrical Shock: The front cover of the panel is to 

be opened only by qualified service personnel.

• The equipment must be installed such that appropriate 

clearance and creepage distances are maintained to con-
form to CE/UKCA/UL  requirements.  Failure to observe 
these requirements may invalidate the CE/UKCA/UL  
conformance.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE/
UKCA requirements in regard to the whole system and 
employ additional protective measures to ensure the CE/
UKCA conformity.

• Install lightning surge protectors for those wires connect-

ed to remote locations.

 

POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

    100 – 240V AC rating: 85 – 264V (90 – 264V for UL), 
     

 

 

 

        47 – 66 Hz, approx. 3 – 5VA

    24V DC rating: 24V ±10%, approx. 2W
  110V DC rating: 85 – 150V (110V ±10% for UL), approx. 2W

 

WARNING!

• To protect very delicate components contained inside 

the unit against damage from static electricity, wear a 
grounded wrist strap when handling them.  If you do not 
have one, touch both of your hands to a safely grounded 
object or to a metal object.

• Ensure that the power supply and input signal are 

switched off before you plug in or remove the unit.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -30 to +60°C   

(-22 to +140°F) with relative humidity within 30 to 90% 
RH in order to ensure adequate life span and operation.

• Be sure that the ventilation slits are not covered with ca-

bles, etc.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 20 minutes is required for 
satisfying complete performance described in the data 
sheet.

Reviews: