M-system Mini-M M2XRP2 Instruction Manual Download Page 5

M2XRP2

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5059  Rev.8  P. 5 / 5

CHANGING I/O TYPE & RANGE

Input type and range, and output type and range can be 
programmed on the Configurator Software.  Additionally, 
when changing the input type, hardware settings are need-
ed as explained below.

UP/DOWN Switches

The front cover cannot be opened to 180 deg. 

when flush with neighboring units.

Configurator Jack

■ 

FRONT VIEW (with cover open)

■ 

LEFT SIDE VIEW (with cover removed)

Input Monitor LED, PL1

Input Monitor LED, PL2

Status Indicator LED

Zero/Span Selector

Top: SPAN

Middle: OFF

Bottom: ZERO

1

4
3
2
1

2

3

4

ON

ON

OFF

OFF ON OFF

ON OFF

SW3

SW1

SW2

SW4

Input Selector SW

Output Selector SW

1
2

1
2

 

DIP SWITCH SETTINGS 

(*) Factory setting
Pulse sensing and noise filter settings are invalid for RS-
422 line driver input.

• Input Type

INPUT TYPE

SW1-2

SW1-1

SW2-2

SW2-1

Open collector (*)

OFF

OFF

OFF

OFF

Voltage pulse

OFF

OFF

OFF

OFF

RS-422 line driver pulse

ON

ON

ON

ON

• Pulse Sensing

PULSE SENSING

SW3-4

SW3-2

Capacitor coupled *

2

OFF

OFF

DC coupled (*)

ON

ON

*2.  Frequency range must be 0 – 100 Hz or higher.  0 – 1 kHz 

or higher for sinusoidal waveform input.  Frequencies 
lower than ±10 Hz may be out of accuracy conformance.

• Noise Filter

NOISE FILTER

SW4-2

SW4-1

With

ON

ON

W/O (*)

OFF

OFF

Be sure to apply the noise filter appropriate for the selected 
frequency range as shown in the table below.  The accuracy 
may not be assured if no filter is applied.

FREQUENCY RANGE

NOISE FILTER TYPE

0 – 10 mHz

With

0 – 100 mHz

With

0 – 1 Hz

With

0 – 10 Hz

W/O

0 – 100 Hz

W/O

0 – 1 kHz

W/O

0 – 10 kHz

W/O

0 – 100 kHz

W/O

• Output Type

OUTPUT TYPE

SW4-4

SW4-3

SW4-2

SW4-1

0 – 20 mA DC (*)

OFF

ON

OFF

OFF

-2.5 – 2.5 V DC

ON

OFF

OFF

ON

-10 – +10 V DC

ON

OFF

ON

OFF

STATUS INDICATOR LED

The M2XRP2 is provided with a status indicator LED which 
blinks in different patterns indicating various status of its 
CPU.
When it is functioning within normal parameters, the LED 
blinks in a regular pattern of ON and OFF.  The high levels 
mean that the LED is ON, while the low levels means OFF 
for as shown in the figure below.

Normal operation

Operating Mode

LED Blinking Pattern

Zero adjustment

Span adjustment

Programming

Abnormal operation

80 msec.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 20 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

Summary of Contents for Mini-M M2XRP2

Page 1: ...ents The equipment must be mounted inside a suitable fire enclosure Altitude up to 2000 meters The equipment must be mounted inside a panel Risk of Electrical Shock The front cover of the panel is to be opened only by qualified service personnel The equipment must be installed such that appropriate clearance and creepage distances are maintained to con form to CE UL requirements Failure to observe...

Page 2: ...e the body from the base socket DIN Rail 35mm wide Spring Loaded DIN Rail Adaptor DIN RAIL MOUNTING Set the base socket so that its DIN rail adaptor is at the bottom Position the upper hook at the rear side of base socket on the DIN rail and push in the lower When removing the socket push down the DIN rail adaptor utilizing a minus screwdriver and pull WALL MOUNTING Refer to EXTERNAL DIMENSIONS TE...

Page 3: ...ch will not be lost even when you turn off power supply to the unit Zero and span are respectively set to 0 and 100 at the factory UP DOWN Switches The front cover cannot be opened to 180 deg when flush with neighboring units Configurator Jack FRONT VIEW with cover open LEFT SIDE VIEW with cover rem Input Monitor LED PL1 Input Monitor LED PL2 Status Indicator LED Zero Span Selector Top SPAN Middle...

Page 4: ...ation 12V DC 5V DC Detect Level 2V 1V DETECTING LEVEL When the parameters have been set with DIP switches and the PC Configurator Software model JXCON a specific sensitivity scale is applied according to the pulse amplitude setting The scaled input voltage is then compared to the preset detecting level 2 00 to 4 00V With DC coupling the scaled maximum voltage must be higher than the detecting leve...

Page 5: ...shown in the table below The accuracy may not be assured if no filter is applied FREQUENCY RANGE NOISE FILTER TYPE 0 10 mHz With 0 100 mHz With 0 1 Hz With 0 10 Hz W O 0 100 Hz W O 0 1 kHz W O 0 10 kHz W O 0 100 kHz W O Output Type OUTPUT TYPE SW4 4 SW4 3 SW4 2 SW4 1 0 20 mA DC OFF ON OFF OFF 2 5 2 5 V DC ON OFF OFF ON 10 10 V DC ON OFF ON OFF STATUS INDICATOR LED The M2XRP2 is provided with a sta...

Reviews: