background image

M2DYH

P. 1 / 2

CURRENT LOOP SUPPLY

(applicable to HART signal)

MODEL

M2DYH

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 PACKAGE INCLUDES:

  Signal conditioner (body + base socket) ...................... (1)

 MODEL NO.

Confirm that the model number described on the product is 
exactly what you ordered.

 INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

  100 – 240V AC rating: 85 – 264V, 47 – 66 Hz, approx. 3.5 – 6.5VA
  24V DC rating: 24V ±10%, approx. 3W
  11 – 27V DC rating: 11 – 27V, approx. 3W
  110V DC rating: 85 – 150V, approx. 3W

 GENERAL PRECAUTIONS

• Before you remove the unit from its base socket or mount 

it, turn off the power supply and input signal for safety.

 ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the air, 

install the unit inside proper housing with sufficient ven-
tilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -5 to +55°C     

(23 to 131°F) with relative humidity within 30 to 90% RH 

in order to ensure adequate life span and operation.

• Be sure that the ventilation slits are not covered with ca

-

bles, etc.

 WIRING

• Do  not  install  cables  (power  supply,  input  and  output) 

close to noise sources (relay drive cable, high frequency 
line, etc.).

• Do  not  bind  these  cables  together  with  those  in  which 

noises are present.  Do not install them in the same duct.

 AND ....

• The unit is designed to function as soon as power is sup

-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

COMPONENT IDENTIFICATION

INSTALLATION

Loosen the fixing screw at the front of the unit in order to 

separate the body from the base socket.

 DIN RAIL MOUNTING

Set the base socket so that 
its DIN rail adaptor is at 
the bottom.  Position the 
upper hook at the rear side 
of base socket on the DIN 
rail and push in the lower.  
When removing the socket, 
push down the DIN rail 
adaptor utilizing a minus 
screwdriver and pull.

 WALL MOUNTING

Refer  to  “EXTERNAL  DI

-

MENSIONS.”

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the con-
nection diagram on the side of the unit.

Model

SPAN

ZERO

Zero Adj.

Span Adj.

Body

Base Socket

Connection

Diagram

Specifications

Fixing Screw

DIN Rail

35mm wide

Spring Loaded

DIN Rail Adaptor

OUTPUT

9

12

13

14

+

+

5

*

*

HHC

HHC

4–20mADC

*

4

R

L

HHC

1

*

Hand-held communicator

INPUT

2-WIRE XMTR

PWR SUPPLY

+

+

1

4

2-WIRE

XMTR

+

5

+

250

Ω

■ 

When Used as DC Supply

■ 

When Used as Isolator

+

+

1

4

5

+

250

Ω

1

INPUT

+

U(+)

V(–)

POWER

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Reviews: