EXTERNAL VIEWS

 FRONT VIEW

 SIDE VIEW

OFF

ON

1 2 3 4

SW1

Output Function

Setting

Zero Adj.

Span Adj.

Status Indicator LED1

Status Indicator LED2

 

DIP SWITCH SETTING

Set the DIP switch to appropriate positions before turning on the power supply.  No change in the switch positions is valid 
while the power is supplied.

• Output Function

Choose the output function: Normal output, or loop test output of 0%, 50% and 100%.

OUTPUT

SW1-1

SW1-2

SW1-3

SW1-4

STAT1 LED

STAT2 LED

Normal (*)

See Table 1

See Table 2

OFF

OFF

ON

OFF

    0%

*1

*1

ON

OFF

OFF

ON

  50%

*1

*1

OFF

ON

Blinking

ON

100%

*1

*1

ON

ON

ON

ON

(*) Factory setting
*1. ON/OFF position is irrelevant.

 

Hold Control Contact Logic 

Table 1

HOLD CONTROL

SW1-1

Hold when the terminals 5 – 8 is open

OFF (*)

Hold when the terminals 5 – 8 is closed

ON

 

Output Limit 

Table 2

OUTPUT LIMIT

SW1-2

Output is NOT limited within 0 to 100%

OFF (*)

Output is limited within 0 to 100%

ON