![M-system Mini-M M2AMS2 Instruction Manual Download Page 3](http://html1.mh-extra.com/html/m-system/mini-m-m2ams2/mini-m-m2ams2_instruction-manual_3137421003.webp)
M2AMS2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5103 Rev.4 P. 3 / 4
EXTERNAL VIEWS
■
FRONT VIEW
■
SIDE VIEW
OFF
ON
1 2 3 4
SW1
Output Function
Setting
Zero Adj.
Span Adj.
Status Indicator LED1
Status Indicator LED2
■
DIP SWITCH SETTING
Set the DIP switch to appropriate positions before turning on the power supply. No change in the switch positions is valid
while the power is supplied.
• Output Function
Choose the output function: Normal output, or loop test output of 0%, 50% and 100%.
OUTPUT
SW1-1
SW1-2
SW1-3
SW1-4
STAT1 LED
STAT2 LED
Normal (*)
See Table 1
See Table 2
OFF
OFF
ON
OFF
0%
*1
*1
ON
OFF
OFF
ON
50%
*1
*1
OFF
ON
Blinking
ON
100%
*1
*1
ON
ON
ON
ON
(*) Factory setting
*1. ON/OFF position is irrelevant.
■
Hold Control Contact Logic
Table 1
HOLD CONTROL
SW1-1
Hold when the terminals 5 – 8 is open
OFF (*)
Hold when the terminals 5 – 8 is closed
ON
■
Output Limit
Table 2
OUTPUT LIMIT
SW1-2
Output is NOT limited within 0 to 100%
OFF (*)
Output is limited within 0 to 100%
ON