TERMINAL CONNECTIONS

Connect the unit as in the diagram below.
Be sure to cross-wire between the Ground terminal (3) and metallic housing of the protected equipment. (100W max.)

MDP-24-1

MDP-65-1

IN

RACK-MOUNTED 

SURGE PROTECTOR

CURRENT LOOP SUPPLY

CENTRAL

STATION

FIELD

(PROTECTED EQUIPMENT)

G

S

S

FROM

FIELD

TO

CENTRAL

STATION

+

3

5

7

1

P–

P+

S–

S+

CABLE

G

G

Connection example with Ch.1 of MGD-24/65 

and model MDP-24-1/65-1.

 

GROUNDING

M-RESTER

PROTECTED

EQUIPMENT

G

G

CROSSOVER WIRE

GROUNDING

(100 ohms or less)

A crossover wire between M-RESTER ground and ground or metallic 

housing of equipment is required for protection.

If the protected equipment has no ground terminal, ground the 

M-RESTER only.