INSTRUCTION MANUAL

LIGHTNING SURGE PROTECTOR FOR MULTI-CHANNEL USE

(high discharge current capacity)

MODEL

MDR2

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Lightning surge protector ...................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

LIMITATION APPLICABLE TO M-RESTER

The M-RESTER will protect electronics equipment from 
damage caused by lightning by absorbing most of the 
surge voltages.
However, M-RESTER may not be effective against cer-
tain extremely high voltages caused by a direct or almost 
direct hit by lightning.
M-RESTER must be installed according to this installa-
tion / instruction manual.

GENERAL

 

FUNCTION & FEATURES

• Protection for semiconductor switches of discrete outputs 

against lightning surge damage

• Applicable to both negative and positive common signals
• Applicable to multi analog signals (non-isolation between 

channels)

• Space saving with multi-channel protectors
• LED monitor indicating degradation of voltage limiter
• LED monitor driven by discrete I/O signal without auxil-

iary power supply

 

SPECIFICATIONS

Max. Continuous operating voltage (Uc)

MDR2

-8NY

-8NA

-8PY

-8PA

Between each of S1 to S8 lines

±30V

Each line to COM*

+30V

-30V

Each line or COM to Earth

±150V

*  MDR2 is operational as an SPD despite less than +2V (for 

MDR2-8PA) or more than -2V (for MDR2-8NA).  However, 
the function of the monitor LED is not guaranteed.

Voltage protection level (Up)

• @1kV / 100A (1.2 / 50µs)

MDR2

-8NY

-8NA

-8PY

-8PA

Between each of S1 to S8 lines ±40V ±50V ±40V ±50V
Each line to COM

+40V +50V

-40V

-50V

Each line or COM to Earth

±500V

• @4kV / 2kA (1.2 / 50µs)

MDR2

-8NY

-8NA

-8PY

-8PA

Between each of S1 to S8 lines

±60V

Each line to COM

+50V +60V

-50V

-60V

Each line or COM to Earth

±600V

Leakage current @max. voltage
  Line to COM

: 5μA

  Line to line

: 5μA

  COM to Earth

: 5μA

Response time

: ≤ 4 ns

Max. discharge current (Imax)
  Line to COM

: 10kA

  Line to line

: 10kA

  COM to earth

: 10kA

Nominal current (I

N

)

: 150mA

Internal series resistance

: 22Ω ±20%

Reviews: