MODEL: MDPA-24

MDPA-24 SPECIFICATIONS

ES-8258 Rev.8   Page 1/4

http://www.m-system.co.jp/

Lightning Surge Protectors for
Electronics Equipment M-RESTER

LIGHTNING SURGE PROTECTOR FOR
STANDARD SIGNAL LINE & PULSE USE

Functions & Features
• Designed specifically for 4 – 20mA DC and
pulse signal line including both 4-wire and 2- wire
transmitters
• Life monitor function helps you to decide when you should
replace the surge protector; reduces maintenance and
prevents downtime
• Pressing CHK (Check) button confirms the degradation
and life span of the surge protection circuits with LEDs
• Absorbs surges only without affecting instrumentation
signal
• No interruption of signal by unplugging surge protector
element

RESTER

MADE IN JAPAN 

SER.NO

BAT

 

ALM

MODEL

MODEL: MDPA–24[1]

ORDERING INFORMATION

• Code number: MDPA-24[1]
 Specify a code from below for [1].
 (e.g. MDPA-24/BN/Q)
• Specify the specification for option code /Q
 (e.g. /C01)

[1]  OPTIONS (multiple selections)

Configuration

blank: With Base (model: SK-2E) included
/BN : Element only for replacement
(Not selectable with DIN rail mounting adapter)

DIN Rail Mounting Adapter

blank: Without
/A33: With adapter (model A-33)

Other Options

blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to M-System's web site.)

/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• Base (model: SK-2E)

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection: M4 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)
Indicators: Activated by CHK (Check) button, see the status
table shown below.
  BAT: Green LED
  ALM: Red LED
Degradation judged: When the leakage current at the
voltage limiter exceed approx. 7.5 μA.
Life time judged: When the number of discharges of the
discharge element reaches the expected life span.
CHK button: Push button; momentary
Battery: Lithium; No recharge or replacement available.
Battery life: 10 years (when used ≤ 2 minutes/month)

Normal

: ON

*

1 : With pulsating line signal or that containing ripples, the LED may 

       flicker or blink when the voltage limiter is degraded. 

: OFF

Normal

Discharged

Normal

Near End

End of Life

Unable to Judge

Normal

Degraded

*

1

No Need

Near

Battery

ALM

BAT

Discharge

Element

Voltage

Limiter

Replacement

Immediately

Required

INSTALLATION

Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 85 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 150 g (0.33 lb), standard
175 g (0.39 lb), with DIN rail mounting adapter

PERFORMANCE

Max. continuous operating voltage (Uc):
 Line to line: 30 V
 Line to earth: ±160 V
Voltage protection level (Up):
• @ 1 kV (100 A)
 Line to line: 45 V
 Line to earth:  ±650 V