TERMINAL CONNECTION

Connect the unit as in the diagram below.
Be sure to cross-wire between the Ground terminal (G) and that of the protected equipment.  When the surge protector is con-
nected with a device which has no ground terminal such like M-System’s, ground the M-RESTER Ground terminal (G) only.

B

G

A

2

C

3

1

MDP-RB

B

G

A

2

C

3

1

MDP-RB

B

+

A

B

RTD XMTR

(PROTECTED EQUIPMENT)

OUTPUT

INPUT

V

U

POWER

A

B

B

RTD

(PROTECTED EQUIPMENT)

 

GROUNDING

M-RESTER

PROTECTED

EQUIPMENT

G

G

CROSSOVER WIRE

GROUNDING

(100 ohms or less)

A crossover wire between M-RESTER ground and the ground or 

metallic housing of the equipment is required for protection.

If the protected equipment has no ground terminal, ground the 

M-RESTER only.

When the M-RESTER is mounted with DIN Rail Mounting Adapter, 

connect the grounding wire to the mounting screw of the M-RESTER.

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.8 N·m

MAINTENANCE

Check surge protectors periodically.  Many cases of light-
ning are ignored, and even lightning at a far distance often 
causes inductive surges.
We recommend that you check your surge protector about 
twice a year, before and after the rainy season.  Check 
whenever you experience a strong lightning occurrence.
Checking procedure is explained in the following:

 

CHECKING

WIRING

1) Make sure that wiring is done as instructed in the con-

nection diagram.

2) Make sure that the Ground terminal (G) is connected to 

the metallic housing of protected equipment.

3) Make sure that the Ground terminal (G) is grounded to 

earth.

DISCHARGE FUNCTION

The M-RESTER Tester is available for checking the ele-
ment module of this surge protector.
If checking of M-RESTER tester shows negative, replace 
the protector.