LIGHTNING SURGE PROTECTOR FOR 

PROFIBUS-PA

MODEL

MDP-PA

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Surge protector ....................................................................(1)
DIN rail mounting adaptor* ...............................................(1)
Screws for DIN rail mounting (M4 × 8)* ...........................(2)
*Included with option code /A33

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

LIMITATION APPLICABLE TO M-RESTER

The M-RESTER will protect electronics equipment from 
damage caused by lightning by absorbing most of the 
surge voltages.
However, M-RESTER may not be effective against cer-
tain extremely high voltages caused by a direct or almost 
direct hit by lightning.
M-RESTER must be installed according to this installa-
tion / instruction manual.

GENERAL

 

FUNCTION & FEATURES

• Designed specifically for PROFIBUS-PA network
• No interruption of transmission signal by unplugging the 

head element module

 

SPECIFICATIONS

LINE TO

LINE

LINE TO

EARTH

SHLD TO

EARTH

Max. continuous
operating voltage Uc)

±27V

±160V

±160V

Voltage protection level
(Up) @2kV (1kA)

±60V

±600V

±600V

Leakage current

≤ 5µA

@±27V

≤ 5µA

@±160V

≤ 5µA

@±160V

Capacitance @1 MHz

≤ 1500 pF

≤ 100 pF

≤ 100 pF

Response time

≤ 4 nsec.

≤ 20 nsec.

≤ 20 nsec.

Max. discharge current
(Imax)

5000A (8 / 20 µs)

Nominal current (IN)

500mA

Internal series resistance

≤ 3.3 Ω including return

Max. line voltage

±27V

POINTS OF CAUTION

 

ENVIRONMENT

• When heavy dust or metal particles are present in the 

air, install the surge protector inside proper housing with 
sufficient ventilation.

• Do not install the surge protector where it is subjected to 

continuous vibration.  Do not subject the unit to physical 
impact.

• Environmental temperature must be within -5 to +55°C     

(23 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

DIELECTRIC STRENGTH TEST

• Loosen the screw located at the left-center of the element 

and remove the element module from the base before 
conducting a dielectric strength testing.  Otherwise the 
element will start discharging at a voltage exceeding the 
max. continuous operating voltage (Uc), which can cause 
insulation failure of the module.

   Be sure to return the element and fasten securely after 

the test.

 

AND ....

• We recommend that you keep spare surge protectors so 

that you can replace them when necessary.

• Lightning surge can enter not only through signal lines 

but also through power supply lines.  We recommend that 
you also use the surge protectors for power line for suffi-
cient protection.

COMPONENT IDENTIFICATION

Ground Terminal (G)
(used as mounting bracket)

Base

Element is secured to Base 
with screw when M-RESTER is 
shipped from Factory.

M•RESTER

MADE IN JAPAN N1430B

Lot.NO

MODEL

Head Element

Specifications