M-system MDP-4R Instruction Manual Download Page 3

MDP-4R

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8232  Rev.5  P. 3 / 3

TERMINAL CONNECTION

Connect the unit as in the diagram below.
Be sure to cross-wire between the Ground terminal (G) and that of the protected equipment.  When the surge protector is con-
nected with a device which has no ground terminal such like M-System’s (See figure below), ground the M-RESTER Ground 
terminal (G) only.

Protected Device

MDP-4R

G

C

B

3

2

MDP-4R

G

G

Protected Device

3

2

C

B

A

1

1

G

+

+

SG

A

LINE

LINE

LINE

LINE

Grounding

≤100

Ω

Grounding

≤100

Ω

*

3

*

1

*

2

*

4

*

4

*

1. Leave Terminal  A  when the shielded twisted-pair cable is not provided.

*

2. Leave Terminal  1  when the protected device has no  SG  (Signal Ground) terminal.

*

3. Cross wire to the surge protector’s  G  terminal when grounding the shield wire. 

*

4. Cross-over wire between  G  terminals of the surge protector and the protected device is required.

      Ground only the surge protector if the protected device has no  G  terminal.

C

B

3

2

MDP-4R

G

+

SG

G

A

1

LINE

LINE

*

1

*

2

*

3

3

2

MDP-4R

G

C

B

A

1

Protected Device

G

+

*

3

LINE

LINE

SG

 

Example: Protected devices have no SG terminals

 

Example: Each SG terminal is connected with triplex cable 

Grounding

≤100

Ω

Grounding

≤100

Ω

Protected Device

*

1. Provide electrical insulation with insulating tape and the like so that the live part is not exposed, 

      as over voltage may generate on the shield wire.

*

2. Cross wire to the surge protector’s  G  terminal when grounding the shield wire. 

*

3. Cross-over wire between  G  terminals of the surge protector and the protected device is required.

      Ground only the surge protector if the protected device has no  G  terminal.

 

GROUNDING

M-RESTER

PROTECTED

EQUIPMENT

G

G

CROSSOVER WIRE

GROUNDING

(100 ohms or less)

A crossover wire between M-RESTER ground and the ground or 

metallic housing of the equipment is required for protection.

If the protected equipment has no ground terminal, ground the 

M-RESTER only.

When the M-RESTER is mounted with DIN Rail Mounting Adapter, 

connect the grounding wire to the mounting screw of the M-RESTER.

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.8 N·m

MAINTENANCE

Check surge protectors periodically.  Many cases of light-
ning are ignored, and even lightning at a far distance often 
causes inductive surges.
We recommend that you check your surge protector about 
twice a year, before and after the rainy season.  Check 
whenever you experience a strong lightning occurrence.
Checking procedure is explained in the following:

 

CHECKING

WIRING

1) Make sure that wiring is done as instructed in the con-

nection diagram.

2) Make sure that the Ground terminal (G) is connected to 

the metallic housing of protected equipment.

3) Make sure that the Ground terminal (G) is grounded to 

earth.

DISCHARGE FUNCTION

The M-RESTER Tester is available for a preliminary check-
ing of the surge protector’s head element.
If any of the above tests shows negative, replace the protec-
tor.