MAINTENANCE

Check M-RESTER periodically. Many cases of lightning are 
ignored, and even lightning at a far distance often causes 
inductive surges.
We recommend that you check your M-RESTER about twice 
a year, before and after the rainy season. Check whenever 
you experience a strong lightning occurrence.
Checking procedure is explained in the following:

 

CHECKING

WIRING

• Make sure that wiring is done as instructed in the con-

nection diagram.

• Make sure that the ground terminal (No. 5 or 10) is con-

nected to the metallic housing of protected equipment.

• Make sure that the ground terminal (No. 5 or 10) is 

grounded to earth.

 

DISCHARGE ELEMENTS

Remove all wiring connected to M-RESTER when you test 
the discharge elements.

• Check resistance across the following terminals on the 

high resistance range of multimeter (infinite standard). 
When measuring across (6) – (7), connect the multimeter 
so that positive voltage is applied to (6) terminal.

Terminals (6) – (7), (6) – (10), (7) – (10), 
                  (8) – (10), (9) – (10)

• Check resistance across the terminal (8) – (9) on the high

resistance range of multimeter of 0.3V or less (infinite 
standard).

• Check that discharging occurs across the same terminals 

with a 500V DC megger. (Indicator of the megger reaches 
over-scale.)

• If any of the above tests shows negative, replace the M-

RESTER.