MDCAT-SPE

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8196  P. 2 / 3

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

EXTERNAL DIMENSIONS  unit: mm [inch]

• When mounting, no extra space is needed between units.

38 [1.50] 

90 [3.54]

10 [.39]

10 [.39]

  DIN RAIL

(35mm wide)

(3 [.12])

40 [1.57]

SURGE SIDE

CONNECTOR

PROTECTED SIDE

CONNECTOR

SHIELD TERMINAL (SHLD)

EARTH TERMINAL (G)

35 [1.38]

6 [.24] (4.5 [.18] deep) 

3 2 1

C B A

SHORTCIRCUIT BAR

11

[.43]

50 [1.97]

4.2 [.17]

35 [1.38]

7.3 [.29]

 DIN RAIL

 UNIT

 

CONNECTION DIAGRAM

1

2

3

A

B

C

G

SHLD

+

SHLD

FG

Protected side

Surge Side

MDCAT-SPE

*

1

*

2

*

3, 

*

4

*

1. Use shortcircuit bar to ground the shield.

*

2. If the protected device has an FG terminal, connect to the G terminal of the MDCAT-SPE.

*

3. Use a DIN rail made of steel or copper when connecting to ground via the DIN rail.

*

4. Single mount DIN rail for option code ‘/DR’ is made of aluminum.

 

Connect to ground with ground terminal when this DIN rail is used.

Shielded Cable

Protected Device