Maintenance Forecast Monitor Function 

(Indication and output)

What is “Maintenance Forecast Monitor Function” ?

The power supply unit is equipped with electrolytic capacitors.

The electrolyte inside the electrolytic capacitor penetrates the sealing rubber and evaporates as time passes since it is manufactured ( 1), which causes deterioration of

characteristics such as decreasing the capacitance ( 2), etc.

Due to this deterioration of the characteristics of the electrolytic capacitor, the power supply unit decreases its performance as time passes.

The maintenance forecast monitor function shows an approximate period left for maintenance of the power supply unit due to deterioration of electrolytic capacitors.

When the period left for maintenance that the power supply forecasts reaches the set value, an alarm is indicated and an output signal is triggered.

Use this function to know the approximate replacement timing of the power supply unit.

Note:

THE MAINTENUNCE FORECAST MONITOR FUNCTION INDICATES AN APPROXIMATE PERIOD LEFT FOR MAINTENANCE, BASED ON DETERIORATION OF

THE ELECTROLYTIC CAPACITOR.  IT DOES NOT PREDICT FAILURES CAUSED BY OTHER REASONS.

Principle of operation

The deterioration speed of the electrolytic capacitor varies considerably according to the ambient temperature.  (Generally the speed follows “Rule of Two for every

10

°

C” ; for every 10

°

C increase in temperature the rate of degradation doubles according to Arrhenius’s equation.)  The MDC6-12024A-M2 monitors the temperature

inside the power supply, and calculates the amount of deterioration according to the running hours and inside temperature.  Judging by this amount of deterioration, the

power supply will give the alarm indication and output when the period left for maintenance reaches the set value.

Notes:

1.Due to degradation of internal electronic parts, replace the power supply at least once every 15 years even if indication and output of maintenance forecast monitor are not issued.

2.The maintenance forecast is accelerated or decelerated according to operating conditions. Periodically check indication.

3.The output may turn ON and OFF alternately according to the acceleration or deceleration of Maintenance forecast.

4.

Indication and Output

When the product is purchased, “

ful

” (

3) will be indicated.  As electrolytic capacitors deteriorate, indication changes to “

hlf

” (

4).  After the remaining time to maintenance is

reduced to two years, indication automatically changes to a value (

5), which decreases from “

1.5

” to “

1.0

” to “

0.5

” to “

0.0

” (year) as the running hours increase.

If the maintenance forecast monitor setting is set to a value larger than two years, value indication automatically begins after the remaining time to maintenance is reduced to the set years.

If the remaining time becomes smaller than setting L (which can be set arbitrarily between 0 and 5.0 years), an alarm (

a02

) and the remaining time are indicated alternately.

And an output is given to an external device from a transistor (  Yrs) to notify of the replacement timing, together with indication.  (The output is turned off after the replacement timing is

reached; with no continuity across   and  .)

Notes:

1.The remaining time to maintenance is based on continuous operation, not including the time when the power supply is turned off, and so may take longer to reach than the

actual time indicated.

2.Until the power supply has been turned for about one month in total, indication is fixed at “

ful

” to estimate the extent of deterioration, while the output remains turned

on (with continuity across   and  ).

PERIODIC CHECK

It may takes from several years to several tens of years under general operating conditions for the power supply to give the maintenance forecast monitor alarm. During

operation over an extended period of time, periodically check if the maintenance forecast monitor output (  Yrs) is correctly functioning by the following procedure.

1.Select the operation mode.

2.Check that the output (  Yrs) is turned on (with continuity across   and  ).

3.In the operation mode, press and hold the   (

) and  

M

  (

) keys simultaneously for at least three seconds.

The main display (

) changes to “

a02

.”

An inactive output (  Yrs) (no continuity across   and  ) in the “

a02

” indication  indicates the correct function.

4.Release keys to return to the regular state.

Note:  DC output stays ON while the periodical check.

©All Rights Reserved

EN

Fig. 1

MDC6-12024A-M2

11 12 13

6

10

9

7

8

Undervoltage alarm function

Fig. 2

2

1

L-0.5

:
:

5

4

3

Fig. 3

Remaining years to

maintenance timing

Main display

Capacitance

of capacitor

AC input

Output voltage

Main display

Operation mode

(Selected indication)

a01

   Lowest value of output voltage

Voltage indication

Operation Manual

MODEL

MDC6

Thank you for purchasing this M-System product.

This manual primarily describes precautions

required in operating the power supply.  Before

operating the product, read this manual thoroughly

to acquire sufficient knowledge of the product to

use it safely and correctly.  Keep this manual close

at hand and use for reference during operation.

Read the MDC6 Instruction Manual together with

this manual without fail.

EN

DC POWER

SUPPLY

Fig.3

Nomenclature

Detection value of

Undervoltage alarm

M-SYSTEM CO., LTD.

Undervoltage

output

In case of setting L between 2.5 and 5 years

In case of setting L between

0 and 2 years

Undervoltage alarm Function (Indication)

Fig.2

When output voltage drop is detected, an alarm (

a01

) and lowest output

voltage value are indicated alternately.

The preset value of detection voltage can be changed in the setting

mode.

Further, the alarm is output from the transistor (   DC LOW) to an

external device.

(Upon output voltage alarm: OFF; with no continuity across   and   )

Notes:

1. Operation begins after about 3 seconds since the AC power is

supplied.

2. The alarm is not indicated in the setting mode.

3. Press the  

M

 (

) after the output voltage is restored, to reset alarm

indication.

4. The undervoltage alarm function monitors the output terminal voltage

of the power supply unit.  To check the voltage accurately, measure

the voltage at the load end.

Operation and Function

Name and Function of Each Part

Fig.1

Indicates the measurement or set value.

L

ights up during indication of output current.

Lights up during indication of peak hold current.

Lights up when the output voltage is indicated. 

Blinks during setup of undervoltage alarm value.

Use the up key to change to the setting 

mode or to increase the set value.
Use the down key to change to the setting 

mode or to decrease the set value.

Lights up during indication of maintenance 

forecast monitor.  Blinks during setup of 

maintenance forecast monitor setting. 
Use the mode key to change the indicated 

parameter or reset the peak hold current 

value.

Function

Name

Main display 

V

A

Apk

Yrs

6

Operation

indicator

7

Mode key

8

Up key

9

Down key

10

Mode Change

Power-ON

Press and hold for three seconds or more. 

Or no key operation for 30 seconds or more.

Press and hold      or      for three seconds or more.

Operation mode

Setting mode

Operation Mode

Various states of the power supply unit are indicated.

Note:

The output voltage will be displayed when the power supply is first turned

on after it is received from the factory.  Thereafter, the main display will

be indicated in the same display when shutting down.

Setting Mode

Set various parameters of the power supply unit.

Maintenance forecast 

monitor

Undervoltage alarm

The reverse video indicates

the shipment setting.

18.5 -  

20.0

  

- 27.5(V)

0.1V intervals

0.0 -  

0.5

  

- 5.0(years)

0.5 year intervals

Note:

Press and hold   (

) or   (

) for  two seconds or more to increase or

decrease the value rapidly.

Output Voltage and Current Indication Function

The output voltage and current of the power supply unit are monitored

and indicated.

Note:

Operation begins after about 3 seconds since the AC power is supplied.

Peak Hold Current Indication Function

The maximum output current is memorized and indicated.  The maximum

output current is always updated whatever the indication mode is.  The

peak hold current is retained even if the AC power is turned off.

Note:

Operation begins after about 3 seconds since the AC power is supplied.

Peak Hold Current Reset

Operation mode

Reset

Peak hold current value 

measurement starts

2 seconds

3 seconds or more

EN

Change  over  setting  mode  on  pressing  and 

holding       (   ) or      (   ) for three seconds.

And check the set value of the corresponding point.

(The set value must return to the shipment 

setting. Set the each value again, if neces-

sary.)  The error message will be canceled 

on changing over operation mode again.

No change

No change

No change

No change

Description

Output state

Restoration method

Main display

Noise detected in 

voltage or current

When external noise is cleared,

indication is automatically restored.
When the overheat condition is removed,

indication is automatically restored.

Overheated

Other memory error

Undervoltage alarm set 

value memory error

Turn the AC input off then on again. 

If the product is not reset, contact the dealer.

Memory error of alarm

set value of maintenance

forecast monitor

Shipment setting or 

value set in the 

setting mode again

Setting after restoration

OFF

OFF

OFF

OFF

12

11

12

12

11

6

Notes:

1. External noise is probable as a cause of “

---

” and “

e0

” errors.

2. Incorrect operating conditions, ventilation error, and incorrect mounting direction are probable as a cause of

h,t

” error.

3. If the "

h,t

" error state continues for about three hours, the maintenance forecast monitor function becomes

invalid.  The indication for maintenance forecast monitor remains as "

h,t

" even after the overheat condition is

removed, and the Yrs output ( ) remains OFF (with no continuity across   and  ).  REPLACE THE POWER

SUPPLY IF THIS CONDITION OCCURS EVEN IF THE DC OUTPUT IS CORRECT, AS INTERNAL PARTS

MAY BE DETERIORATED.

Self-diagnostic Function

EN

In the case that the output voltage drops below the set value (19V)

and an alarm is issued

Output voltage

Output current

Peak hold current

Maintenance forecast monitor

At operation indicator (   ) ,

indicates a lit LED.

 indicates a blinking LED.

0969710-6B (Side A)