EM-9222  Rev.6  P. 2 / 2

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the connection diagram on the top of the unit.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

3

4

5

6

2

1

8

7

80 (3.15)

50 (1.97)

107 (4.21)

127 (5)

[3.3 (.13)]

80 (3.15)

20 (.79)

40 (1.57)

50 (1.97)

7.8 (.31)

CLAMP

(top & bottom)

DIN RAIL

35mm wide

2–4.5 (.18) dia.

MTG HOLE

15 (.59) deep

8–M3.5

SCREW

• When mounting, no extra space is needed between units.

 

CONNECTION DIAGRAM

+

SUPPLY OUTPUT

1

2

U

V

POWER

7

8

 

MDC-1 & -2

 

MDC-3

+

– (COM.)

24V REGULATED

1

3

2

U

V

POWER

7

8

+

40V UNREGULATED

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

7 – 8 with a multimeter.

3) Output:  Check voltage across the terminal 1 (+) – 2 (–) or 

3 (+) – 2 (–) with a multimeter.

4) Output:  Check that output load is within the permissible 

limit.

  MDC-1, -2: 50mA max.
  MDC-3: 65mA max. (the total of 24V/40V outputs)

ADJUSTMENT PROCEDURE

Output voltage adjustment is accessible via front potenti-
ometer behind the front cover.

1) Open the front cover so that OUTPUT ADJ. potentiom-

eter is exposed.

2) Connect a multimeter across the output terminal 1 (+) – 

2 (–).

3) Turn the potentiometer clockwise or counterclockwise 

until desired voltage reading is obtained.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.