TERMINAL CONNECTION

Connect the unit as in the diagram below.
Be sure to ground the DIN rail on which the unit is mounted.
This unit, designed to connect shield wires and cross wires of the protected devices to a DIN rail, is NOT used to ground the 
DIN rail.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

8
6
5
4

1
2
3
7

4

1

5

2

6

3

8

7

95 (3.74)

7

(.28)

98 (3.86)

[1.5 (.06)]

8–M3 EURO 

TERMINAL

DIN RAIL

(35 mm wide)

DIN RAIL

ADAPTOR

WIRE INSERTION ANGLE: approx. 20°

57 (2.24)

1.9 (.07)

 

CONNECTION DIAGRAM

2

5

3

6

8

7

1

4

DIN RAIL ADAPTOR

(for grounding)

DIN RAIL

Grounding

DO NOT connect to unused terminals.

*

1. Oxide coating of an aluminium rail may lower the electric conductivity 

 

between this module and the ground.  Use a steel or copper rail.

*

2. Be sure to ground the DIN rail.

 

Recommended grounding resistance ≤100

Ω

*

2

*

1

WIRING INSTRUCTIONS

 

EURO TERMINAL 

Torque: 0.3 N·m
Applicable wire size: 0.2 – 2.5 mm

2

Stripped length: 8 mm

 

CAUTION WHEN WIRING

Hold the module steady at the front when you 
tighten/loosen screw terminals.