MODEL: MAKN
MAKN SPECIFICATIONS
ES-8142 Rev.1 Page 4/6
L
N
G
SPD1
SPD3
Generator
or transformer
Protective device
of the switchgear
Circuit breaker
Protected
device
■
CONNECTION EXAMPLES BY POWER SYSTEMS
Connection examples of MAKF and MAKN are shown as following.
• Single-phase/2-wire connection
• Single-phase/2-wire (three-phase delta connection earthed
in the middle of phases) or single-phase/3-wire connection
L1
N
L2
G
SPD1
SPD1
SPD2
SPD3
Protective device
of the switchgear
Circuit breaker
Protected
device
Generator
or transformer
• Three-phase/3-wire connection (delta)
• Three-phase/4-wire connection (star)
L1
L2
L3
(N)
G
SPD1
SPD1
SPD2
SPD3
Protected
device
Circuit breaker
Protective device
of the switchgear
Generator
or transformer
Protected
device
L1
L2
L3
N
G
SPD1
SPD1
SPD2
SPD2
SPD1
SPD2
Circuit breaker
SPD3
Protective device
of the switchgear
Generator
or transformer
■
ALARM OUTPUT
When the alarm output is to be transmitted remotely via outdoor cables, a surge protector for the signal line is required.
Choose a circuit breaker with alarm output. Configure a logical OR sequence so that the alarm trips when both or either
of the MAKF, MAKN or the breaker alarm trips.
Single-phase/2-wire, 110V AC
MAKF-240x
MAKF-240x
MAKN-220x
MAKN-220x
POWER SYSTEM (e.g.)
SPD1
SPD3
Single-phase/2-wire, 220V AC
Single-phase/2-wire,
110V AC
MAKF-240x MAKF-240x
POWER SYSTEM (e.g.)
SPD1
SPD2
SPD3
MAKN-220x
Single-phase/3-wire,
220/110V AC
MAKF-240x MAKF-240x MAKN-220x
Three-phase/4-wire,
220V AC
MAKF-240x MAKF-240x
POWER SYSTEM (e.g.)
SPD1
SPD2
SPD3
MAKN-220x
Three-phase/4-wire,
440V AC
MAKF-400x MAKF-400x MAKN-220x
Three-phase/3-wire,
220V AC
MAKF-240x MAKF-240x
POWER SYSTEM (e.g.)
SPD1
SPD2
SPD3
MAKN-220x