TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
Attach the CJC sensor together with input wiring to the input terminals. The CJC sensor is not interchangeable. Check that
its serial number is identical to that of the unit.
■
EXTERNAL DIMENSIONS unit: mm (inch)
I/O PINS
17.5 (.69)
48 (1.89)
75 (2.95)
83 (3.27)
■
CONNECTION DIAGRAM
+
–
Installation Base
OUTPUT 1
6
7
8
9
10
11
+
–
+
–
OUTPUT 2
A
POWER
3
1
2
4
B
C
+
–
T / C
CJC
SENSOR
metal leg
model: CJM
comp. leadwire
+
–
green
red
CONFIGURATOR
JACK
D
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) DIP switches: Check the output range selector setting.
3) Power input: Check the power input voltage.
4) Input: Check that the input signal is within 0 – 100% of
the full-scale.
If the thermocouple or its extension wires are broken, the
output goes over 100% (below 0% with downscale) due to
burnout function. Confirm the status indicator LED pat-
tern and check leadwires in such a case.
5) Output: Check that the load resistance meets the de-
scribed specifications.
6) Status indicator LED: Check that it blinks in a regular
pattern.