TERMINAL CONNECTIONS

Connect the unit as in the diagram below.
Attach the CJC sensor together with input wiring to the input terminals.  The CJC sensor is not interchangeable.  Check that 
its serial number is identical to that of the unit.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

I/O PINS

17.5 (.69)

48 (1.89)

75 (2.95)

83 (3.27)

 

CONNECTION DIAGRAM

+

Installation Base

OUTPUT 1

6

7

8

9

10

11

+

+

OUTPUT 2

A

POWER

3

1

2

4

B

C

+

T / C

CJC

SENSOR

metal leg

model: CJM

comp. leadwire

+

green

red

CONFIGURATOR

JACK

D

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) DIP switches:  Check the output range selector setting.
3) Power input:  Check the power input voltage.
4) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

  If the thermocouple or its extension wires are broken, the 

output goes over 100% (below 0% with downscale) due to 

burnout function.  Confirm the status indicator LED pat-

tern and check leadwires in such a case.

5) Output:  Check that the load resistance meets the de-

scribed specifications.

6) Status indicator LED:  Check that it blinks in a regular 

pattern.