M8XR2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5471 Rev.4 P. 2 / 4
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■
EXTERNAL DIMENSIONS unit: mm (inch)
I/O PINS
17.5 (.69)
48 (1.89)
75 (2.95)
83 (3.27)
■
CONNECTION DIAGRAM
+
–
Installation Base
OUTPUT 1
6
7
8
9
10
11
+
–
+
–
OUTPUT 2
1
POWER
CONFIGURATOR
JACK
2
4
A
B
C
A
B
B
RTD
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) DIP switches: Check the output range selector setting.
3) Power input: Check the power input voltage.
4) Input: Check voltage across the terminal A – B with a
sensitive voltmeter (With 20°C or 68°F, approx. 110mV
with Pt 100, approx. 55mV with Pt 50 Ω).
If RTD wires are broken, the output goes over 100% (be-
low 0% with downscale) due to burnout function. Con-
firm the status indicator LED pattern and check lead-
wires in such a case.
5) Output: Check that the load resistance meets the de-
scribed specifications.
6) Status indicator LED: Check that it blinks in a regular
pattern.