TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

I/O PINS

17.5 (.69)

48 (1.89)

75 (2.95)

83 (3.27)

 

CONNECTION DIAGRAM

Installation Base

OUTPUT 1

6

7

8

9

10

11

+

OUTPUT 2

1

2

A

B

POWER

+

INPUT

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input:  Check the power input voltage.
3) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4) Check that the output load is 60V DC/15W at the maxi-

mum.  For maximum relay life with inductive loads, ex-

ternal protection is recommended.

  When used with a multi-channel installation base (e.g. 

M8BS1-16), the ratings derated as following.

 

Terminal block type

: 30V DC @ 0.25A

 

Cable connector type

: 24V DC @ 50mA

ALARM TRIP OPERATION

TRIP

ACTION

OUT

CODE

POWERED

UNPOWERED

INP < SET INP > SET

OUT

1

Hi

1

OFF

ON

OFF

Hi

2

ON

OFF

ON

OUT

2

Lo

1

ON

OFF

OFF

Lo

2

OFF

ON

ON

ADJUSTMENT PROCEDURE

Turn the front thumbwheel SW to indicate desired set-
points in %.
Output 1 is for high trip, while Output 2 is for low.
Monitor LED turn ON when the coil is energized; Output 1 
coil is energized when the input is above the setpoint, while 
Output 2 coil is when the input is below the setpoint.
Relay contact turns ON when the coil is energized with Out-
put Code 1, de-energized with Output Code 2.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.

• Hi Setpoint

   Increase the input signal from a value lower than the set-

point and check that the relay trips at the setpoint.

• Lo Setpoint

   Decrease the input signal from a value higher than the 

setpoint and check that the relay trips at the setpoint.

When the trip points are shifted, please contact M-System’s 
Sales Office or representatives.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

M8SED1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5380  P. 2 / 2