background image

M8BS-16K1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5490-K1  P. 4 / 4

MAINTENANCE

For maintaining AC power supply types, Power Supply 
Units are available as follows:

• 85 – 132V AC single power supply: HDC6-1
• 85 – 132V AC two independent power sources: HDC4-K-R
• 170 – 264V AC single power supply: HDC4-L-R

Power units’ standard life is expected for 10 years with 
average ambient temperature 35°C (95°F) and 1.0A load.  
Contact M-System for use in extremely different conditions.

 

HOW TO REPLACE THE POWER UNIT 

 

(power supply unit code: KK, L)

1) Prepare Power Unit (switching regulator) model HDC4-

K-R or HDC4-L-R.

2) Turn off the power supply connected to the Power Unit.
3) Remove the wire binding and wiring connected to the ter-

minal 1 – 2 and 4 – 5.

4) Loosen and remove the mounting screws 

A

 (4 places).  

Remove also the screws 

B

 behind the base plate, fixing 

the unit to be replaced.

5) Detach the Power Unit from the Installation Base.
6) Remove the mounting screws 

C

 (2 places) from the new 

Power Unit.

7) Separate the new Power Unit from the mounting plate.
8) Attach the new Power Unit to the Installation Base and 

tighten the screws in reverse order as explained above.

A

A

A

A

B

B

B

B

5
4
3
2
1

5
4
3
2
1

C

Mounting Plate

C

A

B

C

1
2
3
4
5

:  Mounting screws with 
   washer, M3 x 6 (4 pls.)
:  Mounting screws with
   washer, M3 x 5 
   (2 pls. per unit)
:  Flat-head mounting 
   screws, M3 x 4 (+) 
   (2 pls.)
:  24V DC (+)
:  24V DC (–)
:  FG
:  AC power input (U)
:  AC power input (V)

■ 

SIDE VIEW OF THE POWER UNIT

■ 

FRONT VIEW

■ 

REAR VIEW

 

HOW TO REPLACE THE POWER UNIT 

 

(power supply unit code: K)

1) Prepare Power Unit (switching regulator) model HDC6-

1.

2) Turn off the power supply connected to the Power Unit.
3) Remove the wiring connected to the terminals 1 – 2 and 

3.

4) Loosen and remove the mounting screws 

A

 (2 places).  

Loosen the mounting screws 

B

 (2 places) and pull out the 

Power Unit in sliding it to the direction pointed by the 

arrow in the figure below.

5) Disconnect the connectors of the Power Unit.
6) Place the new Power Unit in reverse order as explained 

above.

B

B

A

A

1 2 3

A

B

1
2
3

:  Mounting screws with 
   washer, M3 x 6 (2 pls.)
:  Mounting screws with 
   washer, M3 x 10L (2 pls.)
:  AC power input (U)
:  AC power input (V)
:  FG

■ 

FRONT VIEW

Note:  Check that the internal wiring does not get caught 

between other objects when assembling.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.