WIRING INSTRUCTIONS

  • Applicable wire size

     

Solid: 0.2 to 2.5 mm

2

 (0.55 to 1.75 dia.)

     

Stranded: 0.2 to 2.5 mm

2

 (Tinning wire ends may 

     

 

 

     cause contact failure and therefore is not 

     

 

 

     recommended.)

     

Ferruled: 0.2 to 1.5 mm

2

 (0.55 to 1.35 dia.)

  • Expose wire conductors by 8 mm (0.31”).

8 mm

8 mm

3.7 mm dia.

max.

3.7 mm dia.

max.

Wire exposure

Recommended
ferruled wire

• How to Connect Wires

Screwdriver

Wire

Insert a wire.  Confirm that the wire tip hits the bottom and 
tighten the screw with a screwdriver.
Confirm that the wire’s insulation tube is not caught in the 
terminal. (Torque: 0.3 N·m)

Screwdriver

Wire

8 mm

6 mm

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

7 – 8 with a multimeter.

3) Input:  Check  that  the  input  frequency  is  30  Hz  or  less 

for relay contact, 100 kHz or less for other types of input.  

Check also that input pulse is 10 msec. or wider for relay 

contact, 5 µsec. or wider for other types of input.

4) Output: Check that the load resistance meets the de-

scribed specifications as shown below. 

OUTPUT

LOAD REQUIREMENTS

Open collector

50 V DC @ 100 mA max.

Voltage pulse

1.0 kΩ min. for 5 V 
2.4 kΩ min. for 12 V 

4.8 kΩ min. for 24 V

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.