![background image](http://html1.mh-extra.com/html/m-system/m5ts-series/m5ts-series_manual_3130996006.webp)
M5TS
P. 2 / 2
EM-2462 Rev.6
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship
during the 36-month period following the date that such product was originally purchased if such product has been used under
normal operating conditions and properly maintained, M-System’s sole liability, and purchaser’s exclusive remedies, under this
warranty are, at M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is
defective under the terms of this warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the
defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES,
EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICU-
LAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES
OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-
8510, E-mail: [email protected]
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the con-
nection diagram on the front of the unit.
Attach the CJC sensor together with input wiring to the
input terminals. The CJC sensor is not interchangeable.
Check that its serial number is the same as that of the
unit.
■
EXTERNAL DIMENSIONS unit: mm (inch)
■
CONNECTION DIAGRAM
5
6
7
8
1
2
3
4
94 (3.70)
3 (.12)
25 (.98)
41 (1.61)
[3.3 (.13)]
• When mounting, no extra space is needed between units.
DIN RAIL
35mm wide
8–M3.5 SCREW
7.3 (.29)
16 (.63)
CJC SENSOR
(model: CJM)
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
7 – 8 with a multimeter.
3) Input: Check that the input voltage is within 0 – 100% of
full-scale.
If the thermocouple or its extension wires are broken, the
output goes over 100% (below 0% with downscale) due to
burnout function. Check leadwires in such a case.
4) Output: Check that the load resistance meets the de-
scribed specifications.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■
HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 20 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■
CALIBRATION
Warm up the unit for at least 20 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
+
–
OUTPUT
5
6
*
Deleted with B thermocouple
+
–
T/C
comp. leadwire
3
2
4
+
–
CJC
SENSOR
metal leg
model: CJM
*
8
7
U(+)
V(–)
POWER
Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12
www.sentronic.com
Produkte, Support und Service
SENTRONIC
AG