45
M3LU2 OPERATING MANUAL EM-2653-B Rev.0
12.2 PC CONFIGURATOR sOFTWARE
The I/O settings and calibration are configurable with the PC Configurator Software (model: M3LUCFG). It is convenient
to set the same I/O specifications to several units or the items which are not available with the DIP SW configuration or
‘One-Step Cal’ calibration. Whether the I/O settings are available or not depends on the configuration option code and
configuration mode.
A dedicated cable is required to connect the unit to the PC.
PORT
PC CONFIGURATOR CABLE MODEL NO.
RS-232-C
MCN-CON
USB
COP-US
The PC Configurator Software is freely downloadable at M-System’s web site (http://www.m-system.co.jp/).
Software download model No.: M3CFG
■
I/O CONFIGURATION
The following table shows configurable items with the PC Configurator Software. For detailed information on the PC con-
figuration, refer to the M3LUCFG users manual (EM-9197-A).
ITEM
M3LU2-x/A
M3LU2-x/B
PC CONFIGURATION
(SW3-8 ON)
DIP SW CONFIGURATION
(SW3-8 OFF)
Input type
X
----
----
Sensor wires
X
----
----
PV range (upper, lower)
X
----
----
PV damping (time constant)
X
X
----
Burnout
X
----
----
Cold junction compensation
X
----
----
Transfer function
X
X
----
AO type
X
----
----
AO range (upper, lower)
X
----
----
ADC conversion rate
X
X
X
Custom TC
X
----
----
Custom RTD
X
----
----
Linearization table setting
X
X
----
■
CALIBRATION
‘One-Step Cal’ calibration (I/O ranging) and DAC trimming (fine adjustments) are configurable with the PC Configurator
Software regardless of the configuration option code and configuration mode.
■
REMARKs
For detailed information on the PC configuration, refer to the M3LUCFG users manual (EM-9197-A).