background image

M2EXV

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5133-A  Rev.5  P. 4 / 4

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.8 N·m

 

SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG.Co.Ltd, Nichifu Co.,ltd

6 (.24) max

3.3 (.13) max

mm (inch)

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Check DIP switch setting.
3) Power input voltage:  Check voltage across the terminal 

10 – 11 with a multimeter.

4) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

5) Output:  Check that the load resistance meets the de-

scribed specifications.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Without linearization, warm up the unit for at least 10 
minutes.  Apply 0%, 25%, 50%, 75% and 100% input signal.  
Check that the output signal for the respective input sig-
nal remains within accuracy described in the data sheet.  If 
the output signal is out of accuracy, when the input display 
value is out of accuracy, perform the input fine adjustment.  
When the input display value is correct but the output is 
out of accuracy, perform the output fine adjustment.  Refer 
to the operating manual (EM-5133-B), when adjusting with 
front buttons.  Refer to the M2ECFG users manual (EM-
5147), when adjusting with M2E Configurator Software 
(model: M2ECFG).  And then follow the procedure shown 
below.

• INPUT FINE ADJUSTMENT

1) Set the input signal to 0%, and adjust the input display to 

0% by [69] Input Zero fine adjust.

2) Set the input signal to 100%, and adjust the input display 

to 100% by [70] Input Span fine adjust.

3) Again set the simulated input to 0%, confirm the input 

display.

4) If input display is shifted, repeat the procedure from 1) to 

3).

• OUTPUT FINE ADJUSTMENT

1) Set the simulated input to 0%, and adjust the output sig-

nal to 0% by [71] Output Zero fine adjust.

2) Set the simulated input to 100%, and adjust the output 

signal to 100% by [72] Output Span fine adjust.

3) Again set the simulated input to 0%, confirm the output 

signal.

4) If output signal is shifted, repeat the procedure from 1) to 

3).

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

Reviews: