background image

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5133-A  Rev.5  P. 1 / 4

INSTRUCTION MANUAL

Mini-M

SIGNAL TRANSMITTER

(PC programmable)

MODEL

M2EXV

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Signal conditioner (body + base socket) .............................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
detailed operation regarding settings.  For detailed explana-
tions, please refer to the Model M2EXV operating manual 
(EM-5133-B).
The M2EXV is programmable using a PC.  For detailed in-
formation on the PC configuration, refer to the M2ECFG 
users manual (EM-5147).  
The M2ECFG Configurator Software and the operating 
manual (EM-5133-B) are downloadable at M-System’s web 
site: https://www.m-system.co.jp

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• This equipment is suitable for Pollution Degree 2 and In-

stallation Category II (transient voltage 2500V).  Rein-
forced insulation (signal input or output to power input: 
300V) and basic insulation (signal input to output: 300V) 
are maintained.  Prior to installation, check that the insu-
lation class of this unit satisfies the system requirements.

• Altitude up to 2000 meters.
• The equipment must be mounted inside a panel.
• The equipment must be installed such that appropriate 

clearance and creepage distances are maintained to con-
form to CE requirements.  Failure to observe these re-
quirements may invalidate the CE conformance.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures* to ensure the CE con-
formity.
* For example, installation of noise filters and clamp fil-

ters for the power source, input and output connected 
to the unit, etc.

• Install lightning surge protectors for those wires connect-

ed to remote locations.

 

POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

    100 – 240V AC rating: 85 – 264V, 47 – 66 Hz,
     

 

 

 

        ≤ 4.5VA at 100V AC

     

 

 

 

        ≤ 6.5VA at 200V AC

     

 

 

 

        ≤ 8.5VA at 264V AC

    24V DC rating: 24V ±10%, ≤ 2.3W
    110V DC rating: 85 – 150V, ≤ 2.3W

 

GENERAL PRECAUTIONS

• Before you remove the unit from its base socket or mount 

it, turn off the power supply and input signal for safety.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -5 to +55°C     

(23 to 131°F) with relative humidity within 10 to 85% RH 
in order to ensure adequate life span and operation.

• Be sure that the ventilation slits are not covered with ca-

bles, etc.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

• With voltage output, do not leave the output terminals 

shortcircuited for a long time.  The unit is designed to 
endure it without breakdown, however, it may shorten ap-
propriate life duration.

• The edge of the display may be hidden by the frame and 

invisible depending on the view angle.

COMPONENT IDENTIFICATION

Connection Diagram

(Side)

Body

Base Socket

Display

Fixing Screw

(screw for attaching 
the body to the socket)

Mode

Set

Up

Down

Specification

Reviews: