INSTRUCTION MANUAL

DC ALARM

(PC programmable, quad or octad alarm trip)

MODEL

M1EAXV-1

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

DC alarm (body) ..................................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
detailed operation regarding settings.  For detailed expla-
nations, please refer to the Model M1EAXV-1 operating 
manual (EM-6031-B).
The M1EAXV-1 is programmable using a PC.  For detailed 
information on the PC configuration, refer to the M1EACFG 
users manual (EM-5994).  
The M1EACFG Configurator Software and the operating 
manual (EM-6031-B) are downloadable at M-System’s web 
site: http://www.m-system.co.jp

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• This equipment is suitable for Pollution Degree 2, Meas-

urement Category II (output, transient voltage 2500V).  
Prior to installation, check that the insulation class of 
this unit satisfies the system requirements.  Insulation 
class of this unit is as follows.

  Output code: A, B

Input or output to power

Reinforced insulation (300V)

Input to output

Basic insulation (300V)

L1 or L2 alarm output to 
L3 or L4 alarm output to 
L5 or L6 alarm output to 
L7 or L8 alarm output

Basic insulation (300V)

  Output code: C

Input or output to power

Reinforced insulation (300V)

Input to output

Basic insulation (300V)

L1 alarm output to L2 
alarm output to L3 alarm 
output to L4 alarm output

Basic insulation (300V)

• Altitude up to 2000 meters.
• The equipment must be mounted inside a panel.
• The equipment must be installed such that appropriate 

clearance and creepage distances are maintained to con-
form to CE requirements.  Failure to observe these re-
quirements may invalidate the CE conformance.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

• Install lightning surge protectors for those wires connect-

ed to remote locations.

 

POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

    24V DC rating: 24V ±10%, ≤ 6W

 

GENERAL PRECAUTIONS

• Before you remove the unit from its base socket or mount 

it, turn off the power supply and input signal for safety.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -5 to +55°C     

(23 to 131°F) with relative humidity within 10 to 85% RH 
in order to ensure adequate life span and operation.

• Be sure that the ventilation slits are not covered with ca-

bles, etc.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.