background image

L2CA / L2CE

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: 

+81(6)6659-8510  E-mail: [email protected]

EM-1987  Rev.2  P. 3 / 3

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

 

Torque

: 0.8 N·m

CHECKING

  1 ) Terminal wiring:  Check that all cables are correctly 

connected according to the connection diagram.

  2 ) Auxiliary power input voltage:  Check voltage across 

terminal 9 – 10 with a multimeter.

  3 ) Input:  Check that the input shows within 0 – 120% of 

the rated current.
Be sure to short the secondary side of CT or turn off the 
current at its primary side for preventing the CT from 
burning when  the cables are to be disconnected from 
input terminals.
Be sure that the input waveform is sinusoidal to obtain 
proper accuracy for model L2CA.

  4 ) Output:  Check that the load resistance meets the de-

scribed specifications.

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.

 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of suffi-
cient accuracy level.  Turn the auxiliary power supply on 
and warm up for more than 10 minutes.

  1 ) ZERO:  Apply 0% input and adjust output to 0%.
  2 ) SPAN:  Apply 100% input and adjust output to 100%.
  3 ) Check ZERO adjustment again with 0% input.
  4 ) When ZERO value is changed, repeat the above proce-

dure 1) – 3).

  5 ) Go through the above procedure for channels 2.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

Reviews: