background image

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

7 – 8 with a multimeter.

3) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4) Alarm operations:  Check the alarm operations referring 

to the figure below.

5) Output load:  Check that the output load is 380V 

AC/120VA or 125V DC/30W at the maximum .  For maxi-

mum relay life with inductive load, external protection is 

recommended.

Alarm Trip Operation

Terminal No. in parentheses

0

50

100

Input
(%)

Lo Setpoint

Hi Setpoint

Hi Output

(9–10)ON

Lo Output

(1–3)ON

(1–2)ON

(9–11)ON

Trip Operation in Power Failure

: Terminals 1 – 3, 9 – 11 turn ON.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.

• Hi Setpoint

   Increase the input signal from a value lower than the set-

point and check that the trip point remains within the 
accuracy described in the data sheet.

• Lo Setpoint

   Decrease the input signal from a value higher than the 

setpoint and check that the trip point remains within the 
accuracy described in the data sheet.

When the setpoints are shifted, please contact M-System’s 
Sales Office or representatives.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

KSL-x5

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-3613-B  Rev.5  P. 3 / 3

Reviews: