M-system JFX1 Instruction Manual Download Page 4

JFX1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-1671  Rev.6  P. 4 / 4

PROGRAMMABLE ITEMS

The following items can be monitored and programmed.  For detailed explanations, please refer to the Operation Manual for 
Model PU-2x (EM-9255), Section A.

[GROUP 01]

ITEM

MDFY.

DATA INPUT

DISPLAY

CONTENTS

01

S

MAINTENANCE SWITCH (lock command)

0

MTSW: MON.MODE

MONITOR mode: data monitoring only

1

MTSW: PRG.MODE

PROGRAM mode: “P” marked data modifiable

02

P

Alphabets & No.

TG : XXXXXXXXXX

Tag name entry (10 characters max.)

03

P

Number (%)

OUTPER XXX.XX

Output status monitor (%) & simulation output

05

D

No input

INPPER XXX.XX

Input status monitor (%)

10

D

1

1: LINEARIZER

Multi-point linearizer

11

P

LINEARIZATION

0

LNR NO OPT

Without (proportional output)

1

LNR OPTION

With (default setting)

19

P

Percentage

FINZER

Fine zero adjustment
Initial status shows actual bias (%).
When data is entered, output (%) is shown.

20

P

Percentage

FINSPN

Fine span adjustment
Initial status shows actual gain (%).
When data is entered, output (%) is shown.

LINEARIZATION TABLE
[GROUP 02]

ITEM

MDFY.

DATA INPUT

DISPLAY

CONTENTS

00
01

P
P

Percentage
Percentage

X (00): XXX.XX
Y (00): XXX.XX

Input 0 (Linearization point 1)
Output 0 (Linearization point 1)

:

:

:

:

                  :              :

98
99

P
P

Percentage
Percentage

X (49): XXX.XX
Y (49): XXX.XX

Input 49 (Linearization point 50)
Output 49 (Linearization point 50)

[GROUP 03]

ITEM

MDFY.

DATA INPUT

DISPLAY

CONTENTS

00
01

P
P

Percentage
Percentage

X (50): XXX.XX
Y (50): XXX.XX

Input 50 (Linearization point 51)
Output 50 (Linearization point 51)

:

:

:

:

                  :              :

98
99

P
P

Percentage
Percentage

X (99): XXX.XX
Y (99): XXX.XX

Input 99 (Linearization point 100)
Output 99 (Linearization point 100)

Modification Code

D: No modification (writing) possible.  Used only for monitoring (reading).
S: Modifiable at any time.
P: Modifiable only when the MAINTENANCE SWITCH is in the “PRG” mode.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.