FDU

P. 2 / 2

EM-1428 Rev.5

EXTERNAL DIMENSIONS  

mm (inch)

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any calibra-
tion.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.

■ 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient
accuracy level.  Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO:  Apply 0% input and adjust output to 0%.
2) SPAN:  Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above procedure

1) – 3).

POINTS OF CAUTION

■ 

GENERAL

• Before you remove the unit from its base socket or mount it,
turn off the power supply and input signal for safety.

■ 

ENVIRONMENT

• When heavy dust or metal particles are present in the air,
install the unit inside proper housing and ventilate it.
• Do not install the unit where it is subjected to continuous
vibration.  Do not apply physical impact to the unit.
• Environmental temperature must be within -5 to +55

°

C (23

to 131

°

F) with relative humidity within 30 to 90% RH in order

to ensure adequate life span and operation.

■ 

WIRING

• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present.  Do not install them in the same duct.

■ 

AND ....

• The unit is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data sheet.

MAINTENANCE

Regular calibration procedure is explained below:

■ 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%,
50%, 75% and 100% input signal.  Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of
tolerance, recalibrate the unit according to the "ADJUST-
MENT PROCEDURE" explained earlier.

1

2

3

4

7

6

8

5

26 (1.02)

93 (3.66)

15

(.59)

2–4.5 (.18)
HOLE

15 (.59) deep

8–M3.5

SCREW

7.8 (.31)

107 (4.21)

35.4 (1.39)

DIN RAIL
35mm wide

[3.3 (.13)]

CLAMP
(top & bottom)

137 (5.39)

•When mounting, no extra space is needed between units.

26 (1.02)

100 (3.94)

M-SYSTEM WARRANTY

M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System's sole liability, and purchaser's exclusive remedies,
under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty.  To
submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.  M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]

Reviews: