14.2.2 SETTING
Follow the procedure shown below to set the Modbus/TCP slave.
(1) Connect the DL8 with the COP-US cable to the PC to which the DLCFG is installed.
For connection setting, refer to 4.3 IP ADDRESS SETTING.
COP-US
CFG
DLCFG
(2) Start the DLCFG to show the main window.
Click [Download from device] button to read setting from the DL8 and to open “Configuration” window.
Click [Communication] button to open “Communication” menu.
Then click [Modbus/TCP slave] button to open “Modbus/TCP slave” dialog.
Main Window
1.Click
2.Click
Configuration
Communication
3.Click
Modbus/TCP slave
4.Click
(3) See the following table and configure each parameter.
PARAMETER
DESCRIPTION
Mode
Set “Disable” or “Enable” for the Modbus/TCP slave function of DL8.
Port address
Any port can be specified but use 502 normally.
Linger time
Set network timeout.
(4) Click [OK] button to temporarily save the setting.
To enable the setting, return to “Configuration” window and click [Upload to device] button.
NOTE
• To apply the mode and the port address to the DL8, save and restart the device.
• The number of simultaneous connection is four.