EM-6782  Rev.1  P. 3 / 4

 

CONNECTION DIAGRAM

4

3

2

1

13

14

15

16

U(+)

V(–)

POWER

9

10

PORT-A

Shielded

 Twisted-pair Cable

6

5

8

7

DAL4-1

DAL4-2

LINK A

13

14

15

16

U(+)

V(–)

POWER

9

10

FIBER OPTICS

LINK B

FIBER OPTICS

*

Jumper Pin 

+

Jumper Pin

*

+

PORT-B

Shielded

 Twisted-pair Cable

*

Jumper Pin 

+

PORT-C

Shielded

 Twisted-pair Cable

Jumper Pin

*

+

PORT-C

Shielded

 Twisted-pair Cable

Terminating

Resistors

Terminating

Resistor

Terminating

Resistor

DAL4-5, 7

PORT-A TXD

PORT-A RXD

FIBER OPTICS

13

14

15

16

U(+)

V(–)

POWER

9

10

Jumper Pin

*

+

PORT-C

Shielded

 Twisted-pair Cable

Terminating

Resistor

****

**

**

**

**

**

FG

***

12

FG

***

12

FG

***

12

When the unit is located at the end of transmission line via twisted-
pair cable (= no cross-wiring), short across these terminals.  
Do not short them for the one not located at the end.
When the DAL4 is to be connected with the 22LA1 or DLA1 multi 
transmission devices,do not connect the shield wire to the SG 
(4, 8 or 16) but to the FG at the instrumentation panel.
Grounding the FG improves noise immunity of the power and 
transmission lines, and is a recommended practice when the DAL4
is installed where a noise is present.

*

**

***

WIRING INSTRUCTIONS

 

SCREW TERMINAL

Torque: 0.8 N·m

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

9 – 10 with a multimeter.

3) Twisted-pair cable:  CPEV-0.9 dia. or larger.  Check that 

the (+) are connected to (+), (–) are connected to (–).

4) Twisted-pair cable ports:  When the port is located at the 

end of a transmission line, or unused, short across the 

terminating resistors (2 – 3, 6 – 7 or 14 – 15).