WIRING INSTRUCTIONS
•
Applicable wire size
Solid:
0.2 to 2.5 mm
2
(0.55 to 1.75 dia.)
Stranded: 0.2 to 2.5 mm
2
(Tinning wire ends may cause
contact failure and therefore is not recom-
mended.)
Ferruled: 0.2 to 1.5 mm
2
(0.55 to 1.35 dia.)
The following Phoenix Contact terminals are
recommended:
AI 0,25-8YE 0.2 to 0.25 mm
2
AI 0,34-8TQ 0.25 to 0.34 mm
2
AI 0,5-8WH 0.34 to 0.5 mm
2
AI 0,75-8GY 0.5 to 0.75 mm
2
AI 1,0-8RD 0.75 to 1.0 mm
2
AI 1,5-8BK 1.0 to 1.5 mm
2
•
Expose wire conductors by 8 mm (0.31”).
8 mm
8 mm
4 mm dia.
max.
4 mm dia.
max.
Wire exposure
Recommended
ferruled wire
EXTERNAL VIEWS
ON
1
SW1
SW2
2 3 4 5 6 7 8
Input Config. DIP SW
10 11 12
4
5
6
Zero Adj.
Span Adj.
■
FRONT VIEW
■
SIDE VIEW
RANGE CONFIGURATION
CAUTION !
•
With the current input configuration (SW1-1 ON), DO NOT apply voltage input.
•
DO NOT apply voltage exceeding the maximum value of the selected range.
•
Applying voltage input greater than the maximum value of the selected range may cause failure of the unit. Check the
setting before applying the input signal.
■
GENERAL PROCEDURE
First select a coarse range using the internal DIP switches (SW1 and SW2) according to Tables 2 through 5 below.
Then apply simulated 0% and 100% inputs and fine-tune the output range to 4 mA and 20 mA using the front zero and span
adjustments.
■
INPUT TYPE & RANGE
Table 1
INPUT TYPE
MAXIMUM RANGE
SPAN
OFFSET
DC Current
-30 to +30 mA DC
Min. 16 µA, Max. 60 mA
-100 to +80%
DC Voltage
-100 to +100 V DC *
1
Min. 4 mV, Max. 100 V
of the selected range *
2
*1. Refer to Table 3 for the maximum value of selectable ranges.
*2. Max. voltage across the input terminals: 70 V for conform with EU Directive; 60 V for UL approval.