background image

AS4LC

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-1601  Rev.7  P. 4 / 6

 

SENSOR ADJUSTMENTS USING AN ACTUAL LOAD

1) Program Mode
  Set ITEM 01 – DATA 2 to turn the unit into Program 

Mode.

2) Excitation Voltage
  Choose ITEM 05.  Press DATA UP or DOWN key until 

the Data display shows the desired excitation voltage.  

When the value calculated by [Excitation / Resistance] 

exceeds 30 mA, set a voltage value to fit with 30 mA limit.

  [Example]  Max. excitation voltage 

10 V

     

Strain gauge resistance  120 Ω

  If you choose 10 V as the excitation:
         10 V / 120 Ω = 83.3 mA --> out of allowable range
  Then you will choose 3.6 V or less as calculated by the 

equation: 30 mA × 120 Ω = 3.6 V

3) 0% Input Voltage
  Choose ITEM 07.  With no load applied to the sensor, 

press DATA DOWN key until the display value is stabi-

lized (while the computation circuit of the unit conducts 

averaging process).

  DATA display shows the approximate offset voltage.
    Display Value = Sensor Voltage × Internal Coefficient*
4) 100% Input Voltage
  Choose ITEM 08.  With an actual known load, press 

DATA DOWN key until the display value is stabilized 

(while the computation circuit of the unit conducts aver-

aging process).

  DATA display shows the sensor’s sensitivity span.
5) Monitor Mode
  Set ITEM 01 – DATA 1 to turn the unit into Monitor 

Mode.

6) PV Indication
  Press ITEM UP or DOWN key until ITEM display indi-

cates “P”.

If necessary, go to Display Range Scaling, Moving Average, 
and other adjustments.
Set the unit to Monitor Mode with ITEM P displayed other 
than for programming.
* If 100% load is not available, use the load ratio setting. 

 

With 10% load, set ITEM 09 – DATA 10.0 before adjustments.

 

SENSOR ADJUSTMENTS BY ENTERING VALUES

1) Turn the unit into Program Mode.
2) Excitation Voltage
  Choose ITEM 05.  Press DATA UP or DOWN key until 

the DATA display shows the desired excitation voltage.  

When the value calculated by [Excitation / Resistance] 

exceeds 30 mA, set a voltage value to fit with 30 mA limit.

  [Example]  Max. excitation voltage 

10 V

     

Strain gauge resistance  120 Ω

  If you choose 10 V as the excitation:
         10 V / 120 Ω = 83.3 mA --> out of allowable range
  Then you will choose 3.6 V or less as calculated by the 

equation below:

         30 mA × 120 Ω = 3.6 V
3) 0% Input Voltage
  Choose ITEM 07.  With no load applied to the sensor, 

press DATA DOWN key until the display value is stabi-

lized (while the computation circuit of the unit conducts 

averaging process).

  DATA display shows the approximate offset voltage.
         Display Value = Sensor Voltage ≈ Internal Coefficient

4) Sensor’s Sensitivity
  Choose ITEM 06.  Press DATA UP or DOWN key until 

the display shows desired value as specified in the sen-

sor’s specification sheet.

5) Turn the unit into Monitor Mode.
6) Set to ITEM P.
If necessary, go to Display Range Scaling, Moving Average, 
and other adjustments.
Set the unit to Monitor Mode with ITEM P displayed other 
than for programming.

 

DISPLAY RANGE SCALING

[Example]
PV display range 0.0 to 100.0 modified to show -100 to 100

1) Turn the unit into Program Mode.
2) Decimal Point Position
  Choose ITEM 16 – DATA 0.
3) 0% Scaling Value
  Choose ITEM 14 – DATA -100.
  (Negative [–] range is identified with the PL1 turned on.)
4) 100% Scaling Value
  Choose ITEM 15 – DATA 100.
5) Turn the unit into Monitor Mode.
6) Set to ITEM P.

 

TARE ADJUSTMENT

1) Turn the unit into Program Mode.
2) Contact Input Function
  Choose ITEM 18 – DATA 0.
3) Turn the unit into Monitor Mode.
  (ITEM 18 is set to DATA 0 as default.  No need of con-

ducting 1 through 3.)

4) Set to ITEM P.
5) Close across the contact input terminals (Di).
By the above mentioned procedure, the tare value is stored 
in ITEM 10, the PV display shows the value set by 0% Scal-
ing Value, and the transmitter outputs the value set by 0% 
Output.

The above mentioned procedure is applicable to modifica-
tions from default setting.

Summary of Contents for AS4LC

Page 1: ...nform ity Install lightning surge protectors for those wires connect ed to remote locations POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 100 240VAC rating 85 264V 47 66 Hz approx 11VA 24V DC rating 24V 10 approx 8W 110V DC rating 85 150V approx 8W GENERAL PRECAUTIONS Before you remove the unit from its...

Page 2: ...int in engineering unit 2 Quad 20 0 Quad 30 0 Quad 70 0 Quad 80 0 Dual 20 0 Dual 80 0 01 0 1 2 Modification code 0 Data indication only 1 Only ITEM L1 L4 are modifiable 2 All parameters are modifiable 1 02 N A 0 99 Status indication 0 is normally indicated 0 Normal 1 Memory error 10 Out of input range 15 115 03 N A 0 1 2 Input range code 0 S1 0 0 3 0mV V 1 S2 0 0 10 0mV V 2 S3 0 0 30 0mV V User sp...

Page 3: ... 1 60 Time before display turned off minutes 10 20 2 10 99 Power ON delay time seconds 10 21 2 0 99 Alarm ON delay time seconds 0 22 23 24 25 2 2 2 2 0 1 0 1 0 1 0 1 L1 trip operation L2 trip operation L3 trip operation L4 trip operation 0 Lo 1 Hi 0 Lo 1 Hi 0 Lo 1 Hi 2 0 Lo 1 Hi 2 Quad 0 Quad 0 Quad 1 Quad 1 Dual 0 Dual 1 26 27 28 29 2 2 2 2 0 1 0 1 0 1 0 1 L1 coil at alarm 0 Energized 1 De energi...

Page 4: ...5 Press DATA UP or DOWN key until the DATA display shows the desired excitation voltage When the value calculated by Excitation Resistance exceeds 30 mA set a voltage value to fit with 30 mA limit Example Max excitation voltage 10 V Strain gauge resistance 120 Ω If you choose 10 V as the excitation 10 V 120 Ω 83 3 mA out of allowable range Then you will choose 3 6 V or less as calculated by the eq...

Page 5: ... 72 2 83 7 8 31 CLAMP top bottom DIN RAIL 35mm wide 2 4 5 18 dia MTG HOLE 25 98 deep 14 M3 5 SCREW When mounting no extra space is needed between units 12 5 6 14 11 1 10 15 4 3 2 7 9 8 103 4 06 132 5 20 CONNECTION DIAGRAM N O RELAY 14 CONTACT INPUT Di 2 11 N C RELAY 7 U V POWER 14 CONTACT INPUT Di 2 11 7 U V POWER SPDT RELAY L2 OUTPUT L1 OUTPUT COM STRAIN GAUGE INPUT EXC STRAIN GAUGE INPUT EXC 5 3...

Page 6: ...0 Input LL L HH H L2 15 8 ON L3 10 8 ON L4 1 8 ON OFF OFF L1 9 8 ON OFF OFF Alarm Trip Operation Terminal No in parentheses Example with quad N O contacts LL L H HH Trip Operation in Power Failure Output code 2 All relays turn off Output code 3 All relays turn on Output code 5 Terminals 15 8 1 8 turn on MAINTENANCE Regular calibration procedure is explained below CALIBRATION Warm up the unit for a...

Reviews: