AB2

P. 3 / 3

EM-2635 Rev.3

OPERATION

• When the STOP signal from the computer is ON:

The AB2 tracks the computer input.

• When the STOP signal from the computer is OFF:

The AB2 holds the value just before the OFF signal.
The output signal can be increased or decreased manually by
giving UP or DOWN signals ON.  If both UP and DOWN
signals are ON, the output remains held.

CHECKING

1) Terminal wiring:  Check that all cables are correctly

connected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 7

– 8 with a multimeter.

3) Input:  Check voltage across the input terminals 5 (+) – 6

(–) with a multimeter.

4) Output at STOP signal OFF:  The output does not track

the input signal.

5) Output load:  Check that the load resistance meets the

described specifications.

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any calibra-
tion.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.

■ 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient
accuracy level.  Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO:  Apply 0% input and adjust output to 0%.
2) SPAN:  Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above procedure

1) – 3).

The output ramp rate (response time) for UP/DOWN signal
input can be adjusted within approx. 5 to 30 seconds using the
Response Time Adj.
Caution:
DO NOT turn the Response Time Adj. while operating UP/
DOWN buttons.

MAINTENANCE

Regular calibration procedure is explained below:

■ 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%,
50%, 75% and 100% input signal.  Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of
tolerance, recalibrate the unit according to the "ADJUST-
MENT PROCEDURE" explained earlier.

M-SYSTEM WARRANTY

M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System's sole liability, and purchaser's exclusive remedies,
under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty.  To
submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.  M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]

Reviews: