TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the connection diagram on the top of the unit.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

76 (2.99) dia.

40 (1.57)

52.5 (2.07)

1 (.04)

60.9 (2.40)

46 (1.81)

50 (1.97)

4–M3 (.12) TAP

6 (.24) deep

1 2 3 4

5 6

 

CONNECTION DIAGRAM

1

2

A

B

B

RTD

3

5

6

+

LOAD

OUTPUT

24V DC

4 – 20mA DC

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.6 N·m

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Input:  Check voltage across the terminal 1 – 2 with a 

sensitive voltmeter (With 20°C or 68°F, approx. 220mV 

with Pt 100, approx. 110mV with Pt 50Ω).

  If RTD wires are broken, the output goes over 100% (be-

low 0% with downscale) due to burnout function.  Check 

leadwires in such a case.

3) Output:  Check that the load is within the permissible 

limit including wiring resistance.  

Load Resistance (Ω) = 

Supply Voltage (V) – 13 (V)

0.02 (A)

(including leadwire resistance)

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.  Zero and Span adjustments are located behind 
the top cover.  Release the knurled knobs and open the cover.

 

PREPARATION

1) Loosen Screw (A) on top and open the covering.

A

A

1

2

3

4

5

6

SW1

SW3

VR4

VR5

VR1

VR2

SW2

VR3

SW4

SW1 :  0% Input Adjustment
SW2 :  100% Input Adjustment (coarse)
SW3 :  100% Input Adjustment (fine)
SW4 :  Span Selector
VR1  :  Output Zero Adjustment 
VR2  :  Output Span Adjustment
VR3  :  Cancelling RTD Resistance

 

0% TEMPERATURE ADJUSTMENT

1) Adjust SW1 to appropriate position according to Table 

below.

  Check also that 100% temperature to be adjusted is with-

in the available range in the right column of the table.  

(The available range means that for which M-System 

guarantees ±0.2% accuracy.)

2) Connect a digital voltmeter across the terminal 1 (+) – 4 

(–).

3) With minimum (0%) input, adjust output reading to 0 

±0.001V with VR3.

6R