WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.6 N·m

CHECKING

Open the unit’s outdoor enclosure cover when you conduct 
checking of the transmitter.  Be sure to close the cover after 
the checking is complete.

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Input:  Check voltage across the terminal 1 – 2 with a 

sensitive voltmeter (With 20°C or 68°F, approx. 220mV 

with Pt 100, approx. 110mV with Pt 50Ω).

  If RTD wires are broken, the output goes over 100% (be-

low 0% with downscale) due to burnout function.  Check 

leadwires in such a case.

3) Output:  Check that the load is within the permissible 

limit including wiring resistance.  

Load Resistance (Ω) = 

Supply Voltage (V) – 13 (V)

0.02 (A)

(including leadwire resistance)

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained below.  
Zero and Span adjustments are located behind the top cover 
of the unit.  Open the enclosure cover, release the knurled 
knobs at the front of the unit and open the top cover.
After the calibration is complete, be sure to close both cov-
ers.

1

2

3

4

5

6

SW1

SW3

VR4

VR5

VR1

VR2

SW2

VR3

SW4

SW1 :  0% Input Adjustment
SW2 :  100% Input Adjustment (coarse)
SW3 :  100% Input Adjustment (fine)
SW4 :  Span Selector
VR1  :  Output Zero Adjustment 
VR2  :  Output Span Adjustment
VR3  :  Cancelling RTD Resistance

 

0% TEMPERATURE ADJUSTMENT

1) Adjust SW1 to appropriate position according to Table 

below.

  Check also that 100% temperature to be adjusted is with-

in the available range in the right column of the table.  

(The available range means that for which M-System 

guarantees ±0.2% accuracy.)

2) Connect a digital voltmeter across the terminal 1 (+) – 4 

(–).

3) With minimum (0%) input, adjust output reading to 0 

±0.001V with VR3.

• 100°C or Wider Span (180°F or Wider Span)

SWITCH

POSITION

0% TEMPERATURE

100% TEMPERATURE

°C

°F

°C

°F

SW1-1

    0 –   50

  32 – 122

100 – 500

212 – 932

SW1-2

  50 – 100

122 – 212

150 – 350

302 – 662

SW1-3

100 – 150

212 – 302

200 – 400

392 – 752

SW1-4

200 – 250

392 – 482

300 – 500

572 – 932

SW1-5

300

572

500

932

SW1-6

  -50 –    0

 -58 – +32

  50 – 350

122 – 662

SW1-7

-100 – -50 -148 –  -58     0 –   50

  32 – 122

SW1-8

Unused

Unused

SW1-9

Unused

Unused

SW1-10

Unused

Unused

• 50 – 100°C Span (90 – 180°F Span)

SWITCH

POSITION

0% TEMPERATURE

100% TEMPERATURE

°C

°F

°C

°F

SW1-1

    0 –   50

  32 – 122

  50 – 100

122 – 212

SW1-2

  50 – 100

122 – 212

100 – 150

212 – 302

SW1-3

100 – 150

212 – 302

150 – 200

302 – 392

SW1-4

Unused

Unused

SW1-5

Unused

Unused

SW1-6

  -50 –    0

 -58 – +32

    0 –   50

  32 – 122

SW1-7

-100 – -50

-148 – -58

 -50 –     0

 -58 –   32

SW1-8

Unused

Unused

SW1-9

Unused

Unused

SW1-10

Unused

Unused

6BR

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]